BTL6-A/C/E/G500-M _ _ _ _ -PF-S115
Micropulse Transducer in a Flat Profile Housing
6
Calibration procedure (continued)
6.3

Calibration procedure overview

6.3.1

Teach-in

The factory set null point and end point is replaced by a
new null point and end point. The null point and end point
can be set separately, the output gradient changes.
The detailed procedure for teach-in is described
on page 14.
Steps
► Move magnet to the new null position.
► Read new null point by activating the programming
inputs.
⇒ The current end point remains the same.
New null point
Fig. 6-2:
Reading new null point
► Move magnet to the new end position.
► Read new end point by activating the programming
inputs.
⇒ The current null point remains the same.
New end point
Fig. 6-3:
Reading new end point
www.balluff.com
6.3.2
The gradient can be inverted by activating the
programming inputs.
During inverting, the output gradient is inverted. For
example, a rising output gradient is changed to a falling
gradient.
6.3.3
Restoring the transducer to its factory settings.
Before
After
Before
After

Inverting

The detailed procedure for inverting is
described on page 15.

Reset

The detailed procedure for the reset is
described on page 16.