Param.
Description
P275
DO1 Function
(*)
P276
DO2 Function
(*)
P277
DO3 Function
(*)
P278
DO4 Function
P281
Fx Frequency
P282
Fx Hysteresis
P290
Ix Current
P293
Tx Torque
P295
Inverter Rated Current
P296
Line Rated Voltage
P297
Switching Frequency
P299
DC Braking Start Time
P300
DC Braking Stop Time
P301
DC Braking Frequency
P302
DC Braking Current
P303
Skip Frequency 1
P304
Skip Frequency 2
P306
Skip Band
P308
Serial Address
QUICK REFERENCE OF PARAMETERS, ALARMS AND FAULTS
Adjustable Range
0 = Not Used
1 = F* ≥ Fx
2 = F ≥ Fx
3 = F ≤ Fx
4 = F = F*
5 = Not Used
6 = Is >Ix
7 = Is <Ix
8 = Torque >Tx
9 = Torque <Tx
10 = Remote
11 = Run
12 = Ready
13 = No Fault
14 = No F070
15 = Not Used
16 = No F021/F022
17 = Not Used
18 = No F072
19 = 4-20 mA OK
20 = P695 Value
21 = Forward
22 to 23 = Not Used
24 = Ride-Through
25 = Pre-Charge OK
26 = Fault
27 = Not Used
28 = SoftPLC
29 to 34 = Not Used
35 = No Alarm
36 = Without fault and alarm
37 = Application Function 1
38 = Application Function 2
39 = Application Function 3
40 = Application Function 4
41 = Application Function 5
42 = Application Function 6
43 = Application Function 7
44 = Application Function 8
45 = Fire Mode ON
46 = Low Level of Process Variable
47 = High Level of Process Variable
See options in P275
See options in P275
See options in P275
0.0 to 400.0 Hz
0.0 to 15.0 Hz
0.0 to 40.0 A
0 to 200 %
1.1 to 15.2 A
0 = Reserved
1 = 110 - 127 Vac
2 = 200 - 240 Vac | 310 Vdc
3 = Reserved
4 = 380 Vac | 513 Vdc
5 = 415 Vac | 560 Vdc
6 = 440 Vac | 594 Vdc
7 = 480 Vac | 650 Vdc
2.5 to 15.0 kHz
0.0 to 15.0 s
0.0 to 15.0 s
0.0 to 15.0 Hz
0.0 to 100.0 %
0.0 to 400.0 Hz
0.0 to 400.0 Hz
0.0 to 25.0 Hz
1 to 247
Factory Setting
Prop.
13
0
0
0
3.0 Hz
0.5 Hz
1.0 x I
nom
100 %
According to the
ro
Inverter Model
According to the
cfg
Inverter Model
5.0 kHz
cfg, V/f, VVW
0.0 s
V/f, VVW
0.0 s
V/f, VVW
3.0 Hz
V/f, VVW
20.0 %
V/f, VVW
0.0 Hz
V/f, VVW
0.0 Hz
V/f, VVW
0.0 Hz
V/f, VVW
1
cfg
CFW300 | 15