APPENDIX - TECHNICAL SPECIFICATIONS
P047
0
Out of CONFIG status. The HMI and parameters P006 and P680 must not indicate ConF
1
Two or more DIx (P263...P270) programmed for (4 = Forward Run)
2
Two or more DIx (P263...P270) programmed for (5 = Reverse Run)
3
Two or more DIx (P263...P270) programmed for (6 = Start)
4
Two or more DIx (P263...P270) programmed for (7 = Stop)
5
Two or more DIx (P263...P270) programmed for (8 = Direction of Rotation)
6
Two or more DIx (P263...P270) programmed for (9 = LOC/REM)
7
Two or more DIx (P263...P270) programmed for (11 = Accelerate E.P.)
8
Two or more DIx (P263...P270) programmed for (12 = Decelerate E.P.)
9
Two or more DIx (P263...P270) programmed for (14 = 2
10
Reserved
11
Two or more DIx (P263...P270) programmed for (24 = Disable Flying Start)
12
Two or more DIx (P263...P270) programmed for (26 = Programming Off)
13
Reserved
14
Reserved
15
DIx (P263...P270) programmed for (4 = Forward Run) without DIx (P263...P270) programmed for (5 = Reverse Run) or the
opposite
16
DIx (P263...P270) programmed for (6 = Start) without DIx (P263...P270) programmed for (7 = Stop) or the opposite
17
P221 or P222 programmed for (8 = Multispeed) without DIx (P263...P270) programmed for (13 = Multispeed) or the opposite
18
P221 or P222 programmed for (7 = E.P.) without DIx (P263...P270) programmed for (11 = Accelerate E.P) or the opposite
19
P224 programmed for (1 = DIx) OR P227 programmed for (1 = DIx) without DIx (P263...P270) programmed for (1 = Run/Stop)
AND without DIx (P263...P270) programmed for (2 = General Enable) AND without DIx (P263...P270) programmed for (3 = Quick
Stop) AND without DIx (P263...P270) programmed for (4 = Forward Run) AND without DIx (P263...P270) programmed for (6 =
Start)
20
Reserved
21
P221 or P222 programmed for (8 = Multispeed) with DI1 (P263) AND DI2 (P264) OR DI1 (P263) AND DI5 (P267) OR DI1 (P263)
AND DI6 (P268) OR DI2 (P264) AND DI5 (P267) OR DI2 (P264) AND DI6 (P268) OR DI5 (P267) AND DI6 (P268) programmed for
(13 = Multispeed)
22
Minimum Frequency Reference (P133) greater than Maximum Frequency Reference (P134)
23 to 28
Reserved
29
Two or more DIx (P263...270) programmed for (49 = Enable Fire Mode) OR two or more DOx (P275...P278) Programmed for (45
= Fire Mode ON) OR P580 programmed for 1, 2 or 4 (Fire Mode Enabled) without DIx programmed for (49 = Enable Fire Mode)
OR DIx programmed for (49 = Enable Fire Mode) OR DOx programmed for (45 = Fire Mode ON) and P580 programmed for (0 =
Fire Mode Disabled) or (3 = Reserved)
30 to 32
Reserved
33
Parameterization in conflict with DC Bus Compensation. Energy Saver active (P588 value other than zero), Controle VVW ativo
(P202 = 5), Functions Ride-Through or Flying Start are enable (P320 value other than zero)
Table 1.1: Situations for CONFIG status
nd
Table 1.2: Levels of performance monitoring of the DC link voltage
Supply
110 to 127 Vac (P296 = 1)
200 to 240 Vac (P296 = 2)
380 Vac (P296 = 4)
400 to 415 Vac (P296 = 5)
440 to 460 Vac (P296 = 6)
480 Vac (P296 = 7)
Table 1.3: Overtemperature actuation levels of the power module
Line
Frame Size
Level A050
200 V
A
90 °C (194 °F)
200 V
B
116 °C (248 °F)
400 V
A, B and C
100 °C (212 °F)
Condition
Ramp)
Level F021
Level F022
200 Vdc
460 Vdc
200 Vdc
410 Vdc
385 Vdc
800 Vdc
405 Vdc
800 Vdc
446 Vdc
800 Vdc
486 Vdc
800 Vdc
Level F051
100 °C (212 °F)
126 °C (258 °F)
110 °C (222 °F)
APPENDIX
CFW300 | 29