7 – Wiring
(continued)
1
7-4 External Battery Cabinet Wiring Diagrams
2
3
4
5
6
7
7-5 Electrical and Cable Data
8
Model
SU20KX
9
SU40KX
SU60KX
10
SU80KX
11
12
13
14
200706017 93-2688 SU manual 4C.indd 18
200706017 93-2688 SU manual 4C.indd 18
(continued)
Input
Output
220/380V, 230/400V
220/380V, 230/400V
or 240/415V AC, 3O,
or 240/415V AC, 3O,
4-wire + ground, wye
4-wire + ground, wye
220/380V, 230/400V
220/380V, 230/400V
or 240/415V AC, 3O,
or 240/415V AC, 3O,
4-wire + ground, wye
4-wire + ground, wye
220/380V, 230/400V
220/380V, 230/400V
or 240/415V AC, 3O,
or 240/415V AC, 3O,
4-wire + ground, wye
4-wire + ground, wye
220/380V, 230/400V
220/380V, 230/400V
or 240/415V AC, 3O,
or 240/415V AC, 3O,
4-wire + ground, wye
4-wire + ground, wye
Input, Reserve
and Output
Battery Fuse
Breaker Size
50A
75A
125A
150A
18
Input, Reserve,
Output and Battery
Size
Cable Size
60A
14 mm²
120A
14 mm²
160A
22 mm²
220A
38 mm²
11/29/2007 2:02:37 PM