7 – Wiring

7-6 External Battery Cabinet Wiring

Warning: External battery cabinets vary. Read the external battery cabinet's documentation before attempting to connect it to the UPS
system. Use only external battery cabinets that have been approved by Tripp Lite.
Note: An external battery cabinet is required with models SU60KX and SU80KX. It is optional with models SU20KX and SU40KX. Contact Tripp
Lite for external battery cabinet ordering information.
De-energize all input and output (AC and DC) of the UPS system
1
and external battery cabinet, and confirm that the external battery
cabinet breaker switch
been wired to an AC power source, see
instructions.)
2
Remove the terminal block covers from the UPS system and
external battery cabinet.
3
Connect the positive (+), neutral (N) and negative (-) UPS
system connection terminals of the external battery cabinet to the
corresponding positive (+), neutral (N) and negative (-) external
battery connection terminals of the UPS system. See
and the external battery cabinet's documentation for terminal
block diagrams. See
7-5
for cable size requirements. Cabling should be protected by
flexible conduit and routed through the appropriate knockouts in
the terminal block cover. Warning: Observe proper polarity by
connecting negative to negative and positive to positive. Failure
to observe proper polarity will damage the UPS system and
create a risk of personal injury and property damage.
Connect the external battery cabinet's grounding terminal
4
UPS system's corresponding grounding terminal
(5.189 mm) ground cable. Keep the ground cable connected at all
times after installation.
5
Connect the UPS system's grounding terminal
earth ground
with a 4 AWG (5.189 mm) ground cable. Keep the
B
ground cable connected at all times after installation.
Replace the terminal block cover of the external battery cabinet. If
6
you do not plan to wire the AC input/output of the UPS system at
this time, replace the terminal block cover of the UPS system.
B
5
200706017 93-2688 SU manual 4C.indd 19
200706017 93-2688 SU manual 4C.indd 19
(continued)
A
is off. (If the UPS system has already
Section 9-6
for shutdown
Section 7-3
Section 7-4
for wiring diagrams. See
B
with a 4 AWG
A
to your facility's
A
1
2
+N–
Section
3
to the
A
A
4
6
19
A
+N–
+N–
1
2
3
4
5
6
7
8
9
10
11
B
12
13
14
11/29/2007 2:02:38 PM
11/29/2007 2:02:38 PM

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Smartonline su40kxSmartonline su60kxSmartonline su80kx

Tabla de contenido