By default, this variable is defined by the maximum current of each outlet, which is indicated on the charging
station's specification plate. Its value must be a positive, whole number.
It is recommended that the minimum value for this variable matches the maximum current for an outlet.
Example:
input_current = 32;
nominal_current_outlet1
Current settings sent to the vehicle connected to outlet 1.
By default it is the nominal current that shows on the charging station specification plate. Its value must be a
positive, whole number.
Its bottom limit is 6 Amps according to regulations and its top limit is the same as the current of the specification
plate.
For ZE Ready units, the bottom limit is 7 Amps for single-phase versions and 13 Amps for three-phase versions.
If compliance with these ranges is not met its previous value will be preserved.
Example:
nominal_current_outlet1 = 15;
nominal_current_outlet2
Current settings sent to the vehicle connected to outlet 2.
By default it is the nominal current that shows on the charging station specification plate. Its value must be a
positive, whole number.
Its bottom limit is 6 Amps according to regulations and its top limit is the same as the current of the specification
plate.
For ZE Ready units, the bottom limit is 7 Amps for single-phase versions and 13 Amps for three-phase versions.
If compliance with these ranges is not met its previous value will be preserved.
Example:
nominal_current_outlet2 = 15;
start_deferred_charge
Enables the start time of the deferred charge to be programmed. This variable is disabled by default.
To program the start of the deferred charge, a operator.ini file must be uploaded with a variable that has a valid
time programmed.
The format of the variable is 24 hours, set as follows hh:mm:ss.
Example:
start_deferred_charge = "23:05:00";
To disable the end of the deferred charge a operator.ini file must be uploaded containing an empty variable.
Example:
start_deferred_charge = "";
finish_deferred_charge
Enables the end time of the deferred charge program to be programmed. This variable is disabled by default.
To program the end of the deferred charge a operator.ini file must be uploaded with a variable that has a valid time
programmed.
The format of the variable is 24 hours, set as follows hh:mm:ss.
Example:
finish_deferred_charge = "09:55:00";
To disable the end of the deferred charge a operator.ini file must be loaded containing an empty variable.