Installation instructions
3.1 Mounting the valve terminal
The valve terminal can be fastened in H-rails or mounted
on a wall.
Note
In order to guarantee resistance to shocks and vibra-
tion, the maximum distance between the fastening
points must not exceed 280 mm.
3.2 Replacement of the connection block
The valve terminal uses the exchangeable connections of
the CPX system. Replace the sub-base as follows:
1. Loosen the 4 screws in the manifold block
TORX screwdriver size T10.
2. Pull the sub-base
away from the electrical plug connector.
3. Insert the new sub-base. Tighten the 4 screws of
the sub-base (tightening torque of the screws
0.65 Nm
4. Make the necessary connections. Seal unused connec-
tions with protective caps.
Note
The sub-base CPX-AB-4-M12x2-5POL (-R) must not be
used.