6.
Parameter Object
The DeviceNet Module supports parameter objects through explicit messaging. Soft starter parameters can be uploaded (written) and
downloaded (read) using DeviceNet management software. When the DeviceNet Module is powered up, it automatically obtains
parameter information from the soft starter.
Table 6-1 Parameter object details
Detail
Value (Hex)
Class
0F
Instance
1 to xxx
Attribute ID
01
Get Service
0E
Set Service
10
Only available on Digistart IS soft starters. For parameter details, see the soft starter User Manual.
NOTE
7.
Specifications
Enclosure
Dimensions ........................................................................................................................... 35 mm (W) x 157 mm (H) x 90 mm (D)
Weight ..................................................................................................................................................................................... 250 g
Protection .................................................................................................................................................................................. IP20
Mounting
Spring-action plastic mounting clips (x 2)
Connections
Soft starter ......................................................................................................................................................... 6-way pin assembly
Network ................................................................................................... 5-way male and unpluggable female connector (supplied)
Maximum cable size ............................................................................................................................................................ 2.5 mm
Contacts ........................................................................................................................................................................... Gold flash
Settings
Node address (MAC ID)
Setting ............................................................................................................................................................. Rotary switches
Range ............................................................................................................................................. 0 to 63 (63, factory default)
Data rate
Setting ................................................................................................................................................................. Rotary switch
Options .......................................................................................................... 125 kB, 250 kB, 500 kB (125 kB, factory default)
Power
Consumption
steady state .................................................................................................................................................... 19 mA at 25 Vdc
......................................................................................................................................................................... 31 mA at 11 Vdc
in-rush (at 24 Vdc) .............................................................................................................................. 1.8 A maximum for 2 ms
Galvanically isolated
Certification
CE
.......................................................................................................................................................................... IEC 60947-4-2
C
......................................................................................................................................................................... IEC 60947-4-2
10
Parameter object address
xxx = maximum soft starter parameter number
Always 0x01
Read single soft starter parameter value
Write single soft starter parameter value
www.controltechniques.com
Comment
DeviceNet Module User Guide
2