Figure 2-2 Remove the module from the starter
Remove the module using the following procedure:
1.
Take the module off-line.
2.
Remove the DeviceNet connector.
3.
Remove control power and mains supply from the soft starter.
4.
Push a small flat-bladed screwdriver into the slots at the top and bottom of the module
and depress the retaining clips.
5.
Pull the module away from the soft starter.
3.
DeviceNet Module Connection and Configuration
3.1
Adjustment
The factory default settings for the rotary adjustment switches are:
Figure 3-1 Adjustment switches
Changes to the rotary switch settings take effect when the DeviceNet network is next powered up.
The Data Rate and Node Address (MAC ID) must be set locally on the module. These cannot be set using DeviceNet
NOTE
management software.
When the Data Rate and MSD Node Address (MAC ID) rotary switches are set on PGM position, the module uses the
previously used valid on-line Data Rate and Node Address (MAC ID).
DeviceNet Module User Guide
Issue 1
DATA RATE
500 kB
PGM
250 kB
125 kB
NODE ADDRESS
( 00 - 63, PGM )
2
4
0
6
PGM
MSD
2
4
0
6
8
LSD
www.controltechniques.com
5