3.2
Connections
Figure 3-2 DeviceNet Module connections
Digistart CS
3
Digistart CS
DeviceNet Module
Standard connection onto DeviceNet network
For the DeviceNet Module to accept serial commands, a link must be fitted across terminals CSL-DI2 on Digistart CS starters.
Input links are required across terminals DI2, +24V and DI3, +24V if the Digistart IS soft starter is being operated in Remote mode. In
Local mode, links are not required.
Digistart IS Pr 3O Comms in Remote selects whether the soft starter will accept Start, Stop or Reset commands from the
NOTE
Serial Network Master while in Remote mode. See the Digistart IS User Manual for parameter details.
3.3
Module and network LEDs
The Module LED indicates the condition of the power supply and module operation.
The Network LED indicates status of the communication link between the DeviceNet Module and the network Master.
Figure 3-3 Feedback LEDs
1
2
When a communications failure occurs, the soft starter may trip if the Communication Timeout parameter for the network is
NOTE
set greater than zero. When communication is restored, the soft starter must be reset.
6
1
2
LED
State
Off
Green
(Module)
Red
Red/Green flashing
Off
Green flashing
(Network)
Green
Red flashing
Red
Red/Green flashing
www.controltechniques.com
Digistart IS
3
Digistart IS (Remote mode)
DI2, +24V: Stop
DI3, +24V: Reset
DeviceNet Module
Standard connection onto DeviceNet network
Description
Network power off
Normal operation
Unrecoverable fault
Self Test mode
Duplicate MAC ID test has not been completed
Online but no connection with Master
Online and allocated to a Master
One or more timed out I/O connections
Failed communication between module and Master
Communication faulted and received an Identity communication
faulted request
1
2
DeviceNet Module User Guide
Issue 1