Eaton ECOSENSE LDCM-PL-120-277-010V-GR Instrucciones De Instalación página 3

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

0-10VDC and Resistance Dimming
Connect the purple wire to the + side and the grey to the - side of the 0-10V data signal.
Parameters
Minimum
Source current out of
0-10V (+) Purple wire
Absolute voltage
Range on 0-10V (+)
Purple wire
Sink current into
0-10V (+) Purple wire
(+) Purple wire
LDCM
(-) Grey wire
C
onnec on of LDCM and resistance dimmer
ELV
LIGHTING LOAD (1)
*The maximum cable distance between LDCM and Dimmer is 20M (66ft)
Installation Instructions - LDCM - Plenum Rated: 0-10V, 450W/120V, 1000W/277V
Maximum
0mA
-20V
-19mA
LDCM
Connec on of LDCM and 0-10V analog
dimming
HOT
RED
NEUTRAL
GREY
LDCM
BLACK
WHT/ORG or WHT/BLK
Neutral
BLACK - Hot
(120/277VAC)
BLUE - Relay In
(120/277VAC)
YELLOW
Emergency Power OUT
BLUE - Emergency Power In
(120/277VAC)
Violet - Dimmer 1
Gray - Dimmer 1
1mA
20V
7mA
(+) Purple wire
V
(-) Grey wire
LDCM NOTE:
The EcoSense LDCM module
takes a 0-10V dimming signal and
fixed line voltage input and converts
it to a ELV dimmed output for up to
1000W @ 277V or 450W @120V.
The LDCM is rated to mount
directly to a junction box in the
plenum space for easy installation.
YELLOW
6
Switchpack
White
Red
Receptacle
BMS/Out
5
Black
Sensors
Green
Sensors
Slider
Station
4
Wallstations
-
A/V
Mode
+
-
3
Demand
+
Response
-
Alert
+
Mode
-
Time
+
Clock
2
1
Energy Options DIP Switch
Demand Response
Occupancy
Not Used
1 2
3
4
Default 10%
Occ
20%
Vac (default)
30%
40%
0-10V Dimming Outputs
-
-
-
+
+
+
Dimmer 3
Dimmer 2
Dimmer 1
Dimmer 3
-
Dimmer 2
-
Dimmer 1
-
+
+
+
0-10V Dimming
120V receptacle
circuit
SPRC-R-20-120
20A Receptacle
Control
Blue
Red
Black
Brown
OCC-RJ45
(Occupancy Coupler)
Button 1: Load (1),(2),(3) ON, Dimmer 1: 100%,
Dimmer 2: 80%, Dimmer 3: 100%
Scene 1
Zone 1 UP
Button 2: Load (1),(2),(3) ON, Dimmer 1: 80%,
Scene 2
Zone 1 DN
Dimmer 2: 20%, Dimmer 3: 100%
Scene 3
Zone 2 UP
Button 3: Load (1),(2),(3) ON, Dimmer 1: 50%,
Raise
Zone 2 DN
Dimmer 2: 100%, Dimmer 3: 25%
Lower
Zone 3 UP
Button 4: Press and Hold Raises all dimmers
Zone 3 DN
All Off
Button 5: Press and Hold Lowers all dimmers
Button 6: All Loads OFF
RC-6TSB-P4-*
RC-6TSB-ZAD-*
Scene Station
Office Station
Scenes are programmable within the
Room Controller using the Personal
Remote (HHPR-RC) and new
programming is accessed through
the Scene Wallstations.
EATON
IL503004EN Installation Instructions
Daylight sensor
(DSRC-FMOIR)
Dual Technology
Wall Corner
Occupancy/Vacancy Sensor
(OAWC-DT-120W
)
Button 1: Press and hold increase Zone 1 lighting 5%
Button 2: Press and hold decrease Zone 1 lighting 5%
Button 3: Press and hold increase Zone 2 lighting 5%
Button 4: Press and hold decrease Zone 2 lighting 5%
Button 5: Press and hold increase Zone 3 lighting 5%
Button 6: Press and hold decrease Zone 3 lighting 5%
3