Akron TURBOJET Instrucciones De Funcionamiento página 4

Boquillas y picos
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 11
There are many "tell tale" signs that indicate nozzle repair is in order, such as
If any of the above situations are encountered, the nozzle should be taken out of service and repaired, plus tested
by qualified nozzle technicians, prior to placing it back in service.
A. OPERATING INSTRUCTIONS
BALL SHUTOFF
• Open and close slowly.
• To open: Pull the handle toward the inlet.
• To close: Push the handle towards the outlet.
TIP WITH TWIST SHUTOFF
• Open and close slowly.
• To Open: Rotate the pattern sleeve / bumper counterclockwise to the desired spray angle. Note: The tip opens in a
straight stream pattern.
• To Close: Rotate the pattern sleeve / bumper clockwise until it closes.
NOZZLE & TIP
• To change the spray angle rotate the pattern sleeve/bumper. Rotate it clockwise for straight stream and
counterclockwise for wide fog.
• To flush the nozzle, rotate the flow control ring counterclockwise to the FLUSH setting. Rotate slowly back to the
required setting when obstruction is flushed.
• Turbojet nozzles have various flow settings indicated on flow control ring. To change the flow rate, slowly rotate the
flow control ring to the required setting and adjust your engine to provide the rated pressure at the inlet of the
nozzle.
• To determine the required engine pressures to achieve the flow setting, use the following formula: Engine pressure
(EP)= Friction Loss (FL) + Nozzle Pressure (NP) + pressure loss or gains due to elevation (1/2 psi per foot of height
difference).
FOR USE WITH CAFS
• For optimal CAFS Bubble Structure place the TurboJet pattern in straight stream and turn the flow control selection
ring to FLUSH.
B. MAINTENANCE
• After use, flush the nozzle with clean water to clean grit and dirt from around exterior moving parts will allow the
nozzle to operate as designed.
• Over time the seals and turbine teeth may need replaced. This can be accomplished by purchasing the appropriate
Akron repair kit. Use Qualified maintenance mechanics or return the nozzle to Akron Brass for repair.
• Regularly check the baffle screw to be sure it is tight
• Use low temp Lubriplate on metal parts and Parker O-Ring lubricant on O-Rings.
ISO 9001 REGISTERED COMPANY
• Controls that are inoperable or difficult to operate.
• Excessive wear.
• Poor discharge performance.
• Water leaks.
PHONE: 330 . 2 64 . 5 678 or 800 . 2 28 . 1 161 I FAX: 330 . 2 64 . 2 944 or 800 . 5 31 . 7 335 I akronbrass . c om
WARRANTY AND DISCLAIMER: We warrant Akron Brass products for a period of five (5) years after purchase against defects in materials or workmanship . Akron Brass will repair or replace
product which fails to satisfy this warranty . Repair or replacement shall be at the discretion of Akron Brass . Products must be promptly returned to Akron Brass for warranty service .
We will not be responsible for: wear and tear; any improper installation, use, maintenance or storage; negligence of the owner or user; repair or modification after delivery; damage; failure to
follow our instructions or recommendations; or anything else beyond our control . WE MAKE NO WARRANTIES, EXPRESS OR IMPLIED, OTHER THAN THOSE INCLUDED IN THIS WARRANTY
STATEMENT, AND WE DISCLAIM ANY IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR ANY PARTICULAR PURPOSE . Further, we will not be responsible for any consequential,
incidental or indirect damages (including, but not limited to, any loss of profits) from any cause whatsoever . No person has authority to change this warranty .
© Akron Brass Company . 2012 All rights reserved . No portion of this can be reproduced without the express written consent of Akron Brass Company .
revised: 06/15

Publicidad

Tabla de contenido
loading

Tabla de contenido