UPS Monitoring

UPS monitoring is a standard feature of the AS/400 operating system.
QUPSDLYTIM is a timer in the AS/400 that tells the system how long to
run on UPS power before shutting down. Each AS/400 system is initially
assigned a default value for QUPSDLYTIM. A complete description of
QUPSDLYTIM is provided on the AS/400 Information Center Internet
Site at
Powerware
9125 Installation Guide for IBM Applications
®
12. Start the UPS by pressing the On button. The
stops flashing and the bar graph indicators display the
percentage of load being applied to the UPS.
The UPS is now in Normal mode and supplying power to your
equipment.
NOTE The batteries charge to 80% capacity in approximately 2 hours. However, it is
recommended that the batteries charge for 24 hours after installation or long-term
storage.
13.
For the AS/400.
Monitoring feature.
http://publib.boulder.ibm.com/pubs/html/as400/ic2924/info/index.htm
*NOMAX tells the AS/400 to use customized shutdown software, and if none is
available it will begin shutdown immediately when utility power fails. Do not set
QUPSDLYTIM to "*NOMAX" unless you understand the implications of the "*NOMAX"
function as described at the AS/400 Information Center Internet Site.
05146789 A Uncontrolled Copy
S
Set the QUPSDLYTIM system value for the UPS
C A U T I O N
Installation
µ
i ndicator
.
7