CPV-DI01
4.5 Fieldbus baud rate
Use the 8x DIL switch to set the desired baud rate (switch el-
ements 7 and 8)
Set fieldbus baud rate for Festo protocol
31.25 kBaud
62.5 kBaud
ON
ON
CPV Direct provides automatic baud rate detection for all other
protocols.
5
Addressing
Addressing for the CP system with fieldbus direct connection
varies with the protocol. In general:
1. A CPV valve terminal always uses 16 output addresses. A
CP valve location uses two addresses:
– lower address = pilot solenoid 14
– upper address = pilot solenoid 12.
2. CP valve terminals, electronic output or input modules on
the expansion string use 16 output or input addresses each.
Detailed information and examples for addressing the CP sys-
tem can be found in the description "CP Valve Terminal with
direct link Type CPV..-DI01"
16
187.5 kBaud
375 kBaud
ON
ON
9904NH