46
CARACTÉRISTIQUES TECHNIQUES
TECHNICAL CHARACTERISTICS - TECHNISCHE DATEN - CARATTERISTICHE TECNICHE -
TECHNISCHE KENMERKEN - CARACTERÍSTICAS TÉCNICAS - CARACTERÍSTICAS TÉCNICAS
GB
COMPLIANCE
SYSTEM CONNECTION
Supply types / number of wires
Management
Frequency
SUPPLY
CONSUMPTION
Supply
Current circuit
CURRENT (TRMS)
Starting current (Ist)
Minimum current (Imin)
Transition current (Itr)
Reference current (Iref)
Permanent overload (Imax)
Short-term over-current
VOLTAGE (TRMS)
Direct measurement
Permanent overload
POWERS
Active
Reactive
Resolution
ENERGY
Active
Reactive
Total and partial metering
Bidirectional metering (EA+ and EA-)
Resolution
PRECISION
Active energy
TARIFFS
Tariff management
Number of tariffs managed
Tariff exchange input
METROLOGICAL LED
Impulse weight
Colour
DISPLAY
Type
Refresh time
Back-lighting illumination time
List of functions displayed
COUNTIS E42R - Ref.: 538 699 A
European EMC Directive No. 2004/108/EC (15/12/2004)
LV Directive No. 2006/95/EC Dated 12 December 2006
MID Directive 2004/22/EC
EN50470-1/-3 (February 2007)
Single phase 2 wires 230V / Two phase 2 wires 400V
Three phase 3 wires 3x230 V / 3x400 V and Three phase 4 wires
3x230/400 V
Detection of cabling error
50 (+/- 1 Hz)
Autosupplied
< 10 VA or 2 W
< 1.0 VA
1 mA
10 mA
50 mA
1 A
1.2 A
24 A for 0.5 s (EN50470-3 and IEC 62053-21)
230 V AC Phase/Neutral 400 V AC Phase/Phase +/- 15%
230 / 400 V AC +/- 15%
Yes
No
0.1 kW
Yes
Yes
No (0 to 999999.9 kWh)
No
1 kWh
Class C (EN 50470-3)
Yes
2
Yes
10000 impulses / kWh
Red
7 Digit LED with blue back-lighting
1 s
30 s
Cf. table below