5
Instalación eléctrica
Normas de instalación (todas las versiones)
5.3.13
UL-compliant installation
Field Wiring Power Terminals
Short circuit current rating
Branch Circuit Protection
Motor Overload Protection
Device and Line Protection
54
Instrucciones de funcionamiento – MOVIFIT
NOTA
El siguiente capítulo se imprime siempre independientemente del idioma de la publi-
cación presente debido a los requerimientos UL en idioma inglés.
Observe the following notes for UL-compliant installation:
•
Use 75 °C copper wire only.
•
MOVIFIT
®
uses cage clamp terminals.
Suitable for use on a circuit capable of delivering not more than 200,000 rms symme-
trical amperes when protected as follows:
For 240 V systems:
250 V minimum, 25 A maximum, non-semiconductor fuses
or 250 V minimum, 25 A maximum, inverse time circuit breakers
For 500 V systems:
•
MOVIFIT
®
-FC, max. voltage is limited to 500 V.
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For maximum branch circuit protection see table below.
Series
non-semiconductor fuses
®
MOVIFIT
-FC
500 V minimum, 25 A maximum
MOVIFIT
®
-FC is provided with load and speed-sensitive overload protection and ther-
mal memory retention upon shutdown or power loss.
The trip current is adjusted to 140% of the rated motor current.
®
MOVIFIT
-FC: Units in connection with ABOXes MTA...-M11-.. or MTA....-M12-.. are
provided with device protection and line protection.
®
-FC
inverse time circuit breaker
500 V minimum, 25 A maximum