8) CP.JACK CONTROL UNIT
The follows table shows the electrical connections in Fig. 11:
Terminals
Function
L-N-GND
Power supply
MOT
Motor
ENC
ENCODER
ANT-SHIELD
Antenna
SIS
SYNC
COM
Common Inputs
P.P
Step-by-Step
STOP
STOP
PHOT
Photocell
OPEN
Opens
CLOSE
Close
BAR
Sensitive edge
+ 24V -
24 Vdc
BLINK
Flashing
AUX
AUX 1 Auxiliary output
+ BAT-BAT
Batteries
9) PARAMETERS, LOGIC AND SPECIAL FUNCTIONS
The following table describes the individual functions available in the control unit.
MENU
Automatic closure time Active only with "TCA"=ON logic.
TCA
At the end of the time set, the control unit commands a closure manoeuvre.
It adjusts the opening percentage of the motor controlled by the transmitter with the PED function
tped
(pedestrian function). The value is expressed as a percentage (99% complete opening of the door).
It adjusts the partial opening space controlled by the transmitter if saved with the SAIR radio function.
TCA automatic closure has no effect on partial opening.
sair
Partial opening can take place only if the door is completely closed.
Value expressed as a percentage.
fsto
It adjusts motor opening speed (standard speed before the slowing phase).
fstc
It adjusts motor opening speed (standard speed before the slowing phase).
sldo
It adjusts the motor speed during the opening slowing phase*
sldc
It adjusts the motor during the closing slowing phase*.
It sets the start point of the slowing phase in opening.
tsmo
The value is expressed as a percentage on the entire stroke.
It sets the start point of the slowing phase in closure.
tsmc
The value is expressed as a percentage on the entire stroke.
PMO
It adjusts the motor torque during the opening phase*.
PMC
It adjusts the motor torque during the closure phase*.
PSO
It adjusts the motor torque during the opening slowing phase*.
PSC
It adjusts the motor torque during the closing slowing phase*.
Activation time of the led courtesy light (integrated in the control unit) or the AUX1 contact, if the
AUX1 parameter is set to 2. Value expressed in seconds. On each manoeuvre, the light remains
tls
on for the time set. The service light (on), after pressing one of the 3 buttons of the control unit,
turns off and returns to normal operation after 1 and a half minutes.
It sets a short inversion once the closure limit switch point has been reached. It may be useful
spin
to facilitate the manual manoeuvre.
Select the operating mode of the auxiliary output 1 (Free Contact N.O.)
0: Door open light, contact closed with door open, open with door closed, intermittent during
the manoeuvre (Fig. 12)
aux1
1: Second radio channel of the receiver incorporated
2: Courtesy light, the duration of the contact closure is adjustable by the TLS parameter (Fig.13)
3: Zone light, it is on if the door is open
20
Descrizione
Mains input 100÷250Vac 50/60Hz
Pre-cabled motor connection: 24Vdc.
Absolute encoder quick connector
Built-in radio transmitter card antenna connection (ANT-signal/SHIELD-screen).
Rapid connection for SYS synchronisation (optional)
Common for all control inputs.
Step-by-Step button input (N.O. contact) .
Button input STOP (N.C. contact).
Photocell input active in opening and closing (N.C. contact).
Open button input (N.O. contact), you can connect a timer for time slot openings.
Close button input (N.O. contact). .
Input, safety edge. A 8.2 Kohm resistance is pre-installed on the terminals.
Safety edge of the resistive type, 8K2: connect the edge to the terminals by eliminating the pre-installed
resistance, as shown in Figure 14.
Safety edge of the mechanical type: connect the edge in series to the resistance, as shown in Figure 15.
When the safety edge is activated, the door movement is stopped and reversed for around 3sec.
Power supply output accessories 24Vdc/500 mA max.
24Vdc output 15W max. for connection to the flashing light.
Output with N.O. contact configurable by AUX1 operating logic
Terminal input for connection of the back-up batteries (accessory).
Remove the cover in the event of installation.
9.1) PARAMETERS (PAR)
FUNCTION
MIN-MAX-(Default)
MEMO
1-240-(40s)
1-99-(50)
1-10 (3)
50-99 (99)
50-99 (99)
10-50 (25)
10-50 (25)
1-99-(20)
1-99-(20)
1-99-(20)
1-99-(20)
1-99-(30)
1-99-(30)
1-240 (60)
0-20 (3)
0-3-(0)