IMEON INVERTER
Code
Type
AC BACKUP short-circuits. Shutdown the inverter, then unplug the AC BACKUP connector,
then restart the inverter and activate the AC BACKUP by pushing the OK button during 3sec.
63
error_ond
If this error is resolved, the issue comes from a connected device on the AC BACKUP
connector. If the problem remains, please contact your distributor.
Fan failure. Please restart the inverter. If the problem remains, please contact your
64
error_ond
distributor.
AC BACKUP sensor failure. Please restart the inverter. If the problem remains, please
65
error_ond
contact your distributor.
Hardware version detection error. Please restart the inverter. If the problem remains, please
66
error_ond
contact your distributor.
AC Input/Output reversal. This problem may cause a critical electronic damage. Stop the
67
error_ond
inverter and check the AC Grid and AC BACKUP connections are not reversed. If the
problem remains, please contact your distributor.
AC BACKUP undervoltage. Please reboot the inverter and activate the AC BACKUP. If the
68
error_ond
problem remains, please contact your distributor.
AC BACKUP overvoltage. Please reboot the inverter and activate the AC BACKUP. If the
69
error_ond
problem remains, please contact your distributor.
Battery voltage too high. This problem may cause a critical electronic damage. Disconnect
70
error_bat
your battery and check if its specifications comply with inverter. If the problem remains,
please contact your battery distributor.
Battery not connected. Please connect the batteries and check if a breaker/fuse is not open
71
error_bat
between inverter and batteries. If the problem remains contact your battery distributor.
Charging current error. Check battery settings and check the battery connection & voltage. If
72
error_bat
the problem remains, please contact your distributor.
Battery voltage differs from communicated value. There is a communication problem
between inverter and battery BMS. Please reboot the battery and inverter and check the
73
error_bat
good connection of battery communication cable. If the problem remains, please contact
your distributor.
Internal supply failure. Please restart the inverter. If the problem remains, please contact
74
error_ond
your distributor.
CAN communication lost. There is a communication problem between inverter and battery
75
com_lost
BMS. Please reboot the battery and inverter and check the good connection of battery
communication cable. If the problem remains, please contact your distributor.
Battery error reported. Check the battery ID error in OS. ONE, then restart the battery and
76
error_bat
the inverter. If the problem remains contact your battery distributor.
Communication lost between processors. Please reboot the inverter. If the problem remains,
77
com_lost
please contact your distributor.
78
com_lost
Internet connection lost. Check your internet connection.
Battery current exceeds max battery current limit. Please check the good setting of battery
87
error_bat
parameter in OS. ONE. If the problem remains contact your battery distributor.
Power on grid connection overpasses maximum power specification. Please check the
88
error_ond
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
Current on grid connection overpasses maximum power specification. Please check the
89
error_ond
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
Frequency on AC BACKUP exceeds minimum frequency specification. Please check the
90
error_ond
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
Frequency on AC BACKUP exceeds maximum frequency specification. Please check the
91
error_ond
installation, this problem can cause a critical electronic damage. If the problem remains
contact your distributor.
Current on AC BACKUP overpasses maximum current specification. Remove the high
92
error_ond
power devices with inrush power (air conditioner, pumps,...). This problem can cause a
critical electronic damage. If the problem remains contact your distributor.
PV input power overpasses specification. This problem can cause a critical electronic
93
error_ond
damage. Please check the PV sizing, connection and installation. If the problem remains
contact your distributor.
IMEON_installation_guide_rev D.5