SpeedClean FLOWJET Instrucciones De Operacion Y Mantenimiento página 3

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

This warranty excludes accessories, unusual wear, abuse, damage resulting from accident, or unreasonable
use of this machine. For repairs or warranty information DO NOT contact the place of purchase. Contact
SpeedClean® Customer Service at (888) 700-3540. Any unauthorized repairs will void this warranty.
To obtain warranty service a proof of purchase is required and the unit must be returned freight prepaid. This
warranty gives you specific legal rights; you may also have other rights, which vary state to state. SpeedClean®
reserves the right to change product and/or its specifications. Contact the factory for the latest configuration.
Operating Instructions
 Unwrap hose from unit. Attach to output of pump.
 Attach Spray Gun to quick connect on hose.
 Unwrap power cord from unit. Plug into appropriate outlet. Test and reset GFCI.
 Attach water supply hose to unit (2.5 gallons per minute minimum). Make sure screen washer is in place.
 Turn on water. To prime the pump, squeeze the Spray Gun trigger until water exits nozzle for 3 seconds.
Normal Coil Cleaning
 Attach Yellow Rinsing Nozzle (size 1512) to Spray Gun.
 While holding Spray Gun trigger open, flip Power Switch (rear of unit) to "ON" position.
 Spray condenser with plenty water to remove loose debris.
 Remove Yellow Rinsing Nozzle.
 Attach Black Soaping Nozzle (size 2540).
 Make sure chemical pickup hose is in chemical container and the tip is at the bottom.
 Apply water/chemical solution evenly to coils (siphon ratio is approximately 10:1).
 If possible, let coil cleaner chemical sit for recommended time to penetrate into coils and loosen deposits.
 Remove Black Soaping Nozzle, attach Yellow Rinsing Nozzle, and thoroughly rinse coils with clean water.
 When done, flip Power Switch to the "OFF" position and relieve pressure in hose.
General Maintenance and Storage
 If using with coil cleaning chemicals, run clean water through the pump when done.
 Store unit indoors.
 IMPORTANT!! Replace water seals immediately if pump leaks between head and crankcase.