8. BOARD TOPOLOGY
8.1.
Terminals
P1
Power supply
P2
U
V
Voltage sensing
W
A
Current sensing
B
+
Exciter field
-
6
Analogue signal input
8
P
Connection of
Q
external potentiometer
Signal output
OUT
external alarm
GND GROUND
OB+
Connection with
OB-
Varicomp board
8.2.
Potentiometers
Coarse setup of generator voltage.
VOLT
Turn clockwise to increase voltage.
MIN
MAX
Fine setup of generator voltage (±5% of the VOLT setting).
VFINE
Turn clockwise to increase voltage.
MIN
MAX
Setup of the soft start ramp.
START
Turn clockwise to increase the ramp duration.
MIN
MAX
Setup of the Corner Frequency.
FREQ
Turn clockwise to increase the operation frequency threshold.
MIN
MAX
Setup of the Zero Volt frequency.
SLOPE
Turn clockwise to increase the slope of the V/f curve.
MIN
MAX
Setup of the overexcitation threshold.
AMP
Turn clockwise to increase the limitation intervention threshold.
MIN
MAX
Setup of the droop.
PAR
Turn clockwise to increase droop.
MIN
MAX
Setup of regulation stability.
STAB
Turn clockwise to increase the response speed.
MIN
MAX
963857154_H
OUT
Q
P
8
6
B
A
_
OB-
OB+
+
W
V
U
GND
P2
P1
www.repuestosgruposelectrogenos.es
M31FA600A MEC-20
27