Initial settings
1
With the generator shut down, initially position the regulator potentiometers as indicated in the
following figure:
VOLT
MAX
MIN
MIN
where:
 MIN
potentiometer turned completely counter clockwise:
 ½
potentiometer about midway;
 MAX
potentiometer turned completely clockwise.
NOTE: Whenever there is an external potentiometer connected to terminals P and Q, that
potentiometer must be set midway (½).
2
The dip switches must be initially positioned, with the generator off, in relation to the type of machine
and characteristics of the system.
 Block A: position the dip switches as indicated in the following figure:
in which it is assumed that the sensing is 1-phase (for 3-phase sensing, turn dip switch 1 to
the ON position, see Par. 8.3).
 Block B: select the position of the dip switches as indicated in Par. 8.3.
3
With the generator shut down, check that there are at least one and only one of the following
conditions:
 purple jumper between terminals P and Q;
 terminals P and Q connected to an external potentiometer of suitable value (see Par. 9.5).
Voltage setting
4
Start the generator and bring it to nominal speed: the voltage at the output terminals of the generator
must be less than the generator's rated voltage.
5
Turn the VOLT potentiometer clockwise until the generator output voltage reaches a value equal to
about the rated voltage.
6
Using VFINE, fine calibrate the generator voltage so that it is equal to the rated voltage of the
machine. Turn VFINE clockwise to increase the voltage, counter clockwise to decrease it.
Setting the underfrequency limiter
7
Decrease the generator rotation speed to 90% of the nominal speed.
8
Turn the FREQ potentiometer clockwise until both of the following conditions occur:
 the red LED lights up;
 the generator voltage starts to decrease below the rated value of the machine.
9
Return the rotation speed to the nominal value of the machine and check that:
 the red LED goes out;
 the generator voltage is at the rated value.
963857154_H
VFINE
START
MIN
MAX
MAX
MIN
½
MIN
www.repuestosgruposelectrogenos.es
FREQ
SLOPE
AMP
MAX
MAX
MIN
MIN
MIN
MIN
MIN
MAX
BLOCK A
M31FA600A MEC-20
PAR
STAB
MAX
MAX
MIN
MAX
MIN
MIN
MAX
31