24 V ±10% to terminals X210A.1/X210A.2, the function of inputs and outputs
as well as the communication can be parameterized and maintained, even when
mains voltage is off.
Requirements to be met by external power supply
Input voltage range
GB
Rated input current
Peak inrush current
External fuse
Safety
4.3.3 Control terminal X10
Term.
1 ... 3
Relay output, floating change-over contact, response time approx. 40 ms,
maximum contact load:
make contact: AC 5 A / 240 V, DC 5 A (ohmic) / 24 V
break contact:
4.4 X13 connection in ACU510 and ACU610
When an ACU510
is required.
88
DC 24 V ±10%
Max. 1.1 A
Typically: < 25 A
Via standard fuse elements for rated current, characteristic:
slow
Safety extra low voltage (SELV) according to EN 61800-5-1
Control terminal X10
AC 3 A / 240 V, DC 1 A (ohmic) / 24 V
or
ACU610
device is used, connection of AC 3x400 V at X13
Quick Start Guide ACU
Relay output X10
S3OUT Parameterizable relay output
Description
Auxiliary voltage terminal X13
1 ... 6
7
8
9
10
Connection
Connected load
Supply voltage
Supply frequency
Not used
PE
L1
L2
L3
≥ 1.2 kW
400 V +- 10 %
50 / 60 Hz
10/18