Function Diagram
t
t
R
A
t
Emergency Stop
M
single channel
t
= Response time
A
t
= Release time
R
t
= Min. switch-on time
M
Technical data
Supply
Rated voltage U
N
Rated power DC / AC
Rated power AC
Residual ripple U
SS
Rated frequency
Operating range
Control circuit
Isolation between A1, A2 and Y1
Rated output voltage only to supply the inputs
Response time t
K1, K2
A
Release time t
by emergency stop K1, K2
R
Minimum switch-on time t
M
Output circuit
Contacts
Switching voltage U
n
Max. rated current I
/ safety contact
n
Max. total current for all contacts
Application category according EN 60947-5-1
Short-circuit protection
General data
Test voltage
Rated surge voltage
Protection degree Housing/Terminals acc. EN 60529
Isolation
Contamination level
Ambient temperature working range / storage range
Weight
Terminals and connection
Single-core or finely stranded
Stripping length
Finely stranded with wire-end ferrule to DIN 46228
Max. tightening torque
4
A1 Power Supply, LED SUPPLY
A2 Power Supply
Y2 Reset
K1, K2 and LED K1,K2
13/14, 23/24
Emergency Stop
two channel
FD 0221-6 W1
by Y2
DC 24 V
1 W
---
2,4 V
50 Hz to 60 Hz
0.85 to 1.1 x U
no
DC 24 V
20 ms
50 ms
30 ms
2 NO safety contacts positively driven
AC/DC 230 V
4 A
8 A
AC-15: Ue AC 230 V, Ie 3 A
DC-13: Ue DC 24 V, Ie 3 A
fuse element max. 4 A type gG
300 V
4 kV
IP 40 / IP 20
Creepage and clearance between circuits
acc. EN 60664-1
3 external, 2 internal
-25°C to +55°C / -25°C to +75°C
0.2 kg
1 x 0.14 - 2.5 mm² / 2 x 0.14 - 0.75 mm²
max. 8 mm
1 x 0.25 - 2.5 mm² / 2 x 0.25 - 0.5 mm²
0.5 to 0.6 Nm
AC 24 V
1 W
1 VA
--
N