Double ventilation and (OPTIONAL) batteries
Double ventilation:
If the control panel has double ventilation, then it should be connected according to the
following schematic.
-
-
+
+
Vent
Zona2
Alar
In case of 1 or 2 zones Control Panel, you have to follow indications with *
Factory settings are as follows:
Parameter
Ventilation 1 Level:
Ventilation 1 Delay:
Post-ventilation 1 delay:
Ventilation 2 Level:
Ventilation 2 Delay:
Post-ventilation 2 delay:
Alarm Level:
Alarm Delay:
Batteries:
Batteries must be wired to the to the battery output
on the board on the right side of the panel, this
output is labelled.
Two 12V-batteries series-connected:
CCO122 / CCO222 / CCO322 / CCO422
-
-
+
+
Alar
Vent
Zona1
Value
50 ppm
Programmable
(20 150 ppm)
4 min
Programmable
(1 9 min)
4 min
Fixed
200 ppm
Programable
(20 300 ppm) and
Ventilation 1 level
10 min
Programable
(1 30 min) and
Ventilation 1 delay
4 min
Fixed
300 ppm
Fixed
15 min
Programmable
(10 30 min)
FIRE PROTECTION MANUFACTURER
Ctra. de Molins de Rei a Rubí, Km. 8,4 - 08191 RUBÍ (Barcelona) ESPAÑA.
Tlf.: +34 935 862 690 - Fax:+34 936 999 261 - cofem@cofem.com - www.cofem.com
ENGLISH
-
-
+
-
-
+
+
+
Vent
Alar
Vent
Zona1
Alar
Zona2
Margins
Ventilation 2
level
Ventilation 1
level
-
+
12V
-
+
BAT
J1
1
6
Q1
Q2
Q3
Q4
Q5
D3
D4
D1
D2
D5
U3
U4
U2
U1
U5
1
1
1
1
-
+
Vent2Z1
Vent2Z2 Vent2Z3
Vent2Z4
[CO]
Alarm
level
Post-ventilation 2
Delay
Ventilation 2
Delay
Post-ventilation 1
Delay
Ventilation 2
Ventilation 1
Ventilation 1
OFF
Delay
Ventilation 1
Ventilation 1
ON
ON
+
-
-
12V
Alarm
Alarm
Delay
OFF
Alarm
Ventilation 2
ON
OFF
Ventilation 2
ON
ON
Tiempo