6
Programming Menu
EN
Below is a list of parameters applicable to this product. Other
parameters found in the handset should NOT be used. If these are
inadvertently changed, please apply the "Factory Reset" function before
initiating the commissioning process.
DE
Nachfolgend finden Sie eine Liste der Parameter, die für dieses
Produkt gelten. Andere Parameter des Mobilteils sollten NICHT verwendet
werden. Sollten diese versehentlich geändert werden, wenden Sie bitte
vor der Inbetriebnahme die Funktion „Factory Reset" an.
ES
A continuación se muestra una lista de parámetros aplicables a
este producto. NO se deben utilizar otros parámetros que se encuentran
en el teléfono. Si se modifican inadvertidamente, aplique la función
"Factory Reset" antes de iniciar el proceso de puesta en marcha.
PT
Abaixo está uma lista de parâmetros aplicáveis a este produto.
Outros parâmetros encontrados no aparelho NÃO devem ser usados. Se
eles forem alterados inadvertidamente, aplique a função "Reinicialização
de fábrica" antes de iniciar o processo de comissionamento.
UNLCDHS Programming – Detector Parameters
Basic Parameters for EBDHS-B01-DD
Parameter
Timeout
Sensitivity On
Sensitivity Off
Manual Timeout
Walk Test LED
Disable Detect
Power Up State
Inhibit (secs)
Default
Range / Option
20
0 – 99 minutes
9
1 – 9
9
1 – 9
10
0 – 99 minutes
Off
On / Off
No
Yes / No
Yes
Yes / No
1
1 - 99 seconds
FR
Vous trouverez ci-dessous une liste des paramètres applicables
à ce produit. Les autres paramètres trouvés dans le combiné ne doivent
PAS être utilisés. Si ceux-ci sont modifiés par inadvertance, veuillez
appliquer la fonction « Factory Reset » avant de lancer le processus de
mise en service.
IT
Di seguito è riportato un elenco di parametri applicabili a questo
prodotto. Gli altri parametri presenti nel portatile NON devono essere
utilizzati. Se questi vengono modificati inavvertitamente, applicare la
funzione "Factory Reset" prima di avviare il processo di messa in servizio.
NL
Hieronder vindt u een lijst met parameters die van toepassing zijn
op dit product. Andere parameters in de handset mogen NIET worden
gebruikt. Als deze per ongeluk worden gewijzigd, moet u de functie
"Fabrieksreset" toepassen voordat u het inbedrijfstellingsproces start.
How long the lights stay on for after movement has stopped.
This sets both Timeout (channel 1) and Timeout (channel 2) to the same value.
Select 0 for a 10 second delay (use for commissioning only).
Sensitivity level for detecting further movement when the lights are already on.
1 = minimum, 9 = maximum (least movement required to trigger the lights).
Sensitivity level for detecting any movement when the lights are off.
1 = minimum, 9 = maximum (least movement required to trigger the lights).
Sets the time period for the unit to hold its output state after a manual override
command is performed with a handset.
This period is cancelled once motion detection Timeout period ends. If no
movement is ever detected, the Manual Override Cancel command can be
applied to cancel this operation so that the unit is ready to act immediately to
the next motion detection.
When set to On a red LED on the sensor flashes when movement is detected.
Use this feature to check for adequate sensitivity levels.
Disables presence / absence detection, so that the detector can't control
switching but can control dimming output. Use this mode when the unit is for
maintained illuminance only.
Select No for a 40 second delay after initial power up before the detector
starts detecting and changing outputs.
Select Yes for no delay - the detector will always power up detecting.
The time to wait after the detector turns lights off before it can retrigger them.
This inhibit function prevents inadvertent effects of vibrations caused by relay
contact switching movement on highly sensitive models such as microwave
technology sensors. Adjust only if signs of self re-triggering are happening.
Warning: High values would render undesirable delays in the sensor's
response to movement.
Description