To Perform A Test Run; To Perform A Test Run In Winter Season; Disposal - Daikin FTXP20L2V1B Manual De Instalación

Ocultar thumbs Ver también para FTXP20L2V1B:
Tabla de contenido

Publicidad

There are NO loose connections or damaged electrical
components in the switch box.
The insulation resistance of the compressor is OK.
There are NO damaged components or squeezed
pipes on the inside of the indoor and outdoor units.
There are NO refrigerant leaks.
The correct pipe size is installed and the pipes are
properly insulated.
The stop valves (gas and liquid) on the outdoor unit are
fully open.
6.3

To perform a test run

Prerequisite: Power supply MUST be in the specified range.
Prerequisite: Test run may be performed done in cooling or heating
mode.
Prerequisite: Test run should be performed in accordance with the
operation manual of the indoor unit to make sure that all functions
and parts are working properly.
1 In cooling mode, select the lowest programmable temperature.
In heating mode, select the highest programmable temperature.
Test run can be disabled if necessary.
2 When the test run is finished, set the temperature to a normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.
3 The system stops operating 3  minutes after turning the unit
OFF.
6.3.1

To perform a test run in winter season

When operating the air conditioner in Cooling mode in winter, set it
to test run operation using the following method.
For FTXP-L and ATXP-L units
1 Press
,
, and
2 Press
.
3 Select
.
4 Press
.
5 Press
or
to switch the system on.
Result: Test run operation will stop automatically after about
30 minutes.
6 To stop operation, press
For FTXF-A units
7 Press to switch the system on.
8 Press the centre of
,
9 Press
twice.
Result:
will appear on the display. Test run operation is
selected.
Result: Test run operation will stop automatically after about
30 minutes.
10 To stop operation, press .
INFORMATION
Some of the functions CANNOT be used in the test run
operation mode.
If a power failure occurs during operation, the system automatically
restarts immediately after power is restored.
(A)(F)TXP20~35L2V1B + FTXF20~71A2V1B
Daikin room air conditioner
3P512025-1 – 2017.11
simultaneously.
.
, and
simultaneously.
7

Disposal

Dismantling of the unit and treatment of the refrigerant, oil and other
parts MUST comply with the applicable legislation.
7 Disposal
Installation manual
15