Commissioning; Checklist Before Commissioning; To Perform A Test Run; To Perform A Test Run In Winter Season - Daikin FTXP20M5V1B Manual De Instalación

Ocultar thumbs Ver también para FTXP20M5V1B:
Tabla de contenido

Publicidad

INFORMATION
▪ In case you could NOT complete the setting in time,
turn the power supply off and wait at least 1  minute
before turning the power supply back on.
4 Press simultaneously:
Model
Buttons
FTXP and ATXP
5 Press:
Model
Button
FTXP and ATXP
6 Select:
Model
Symbol
FTXP and ATXP
7 Press:
Model
Button
FTXP and ATXP
ON/OFF
a
Operation lamp
b
ndoor unit ON/OFF switch
8 Press the indoor unit ON/OFF switch while the operation lamp
is blinking.
Jumper
Address
Factory setting
1
After cutting with nippers
2
INFORMATION
If the setting could NOT be completed while the operation
lamp was blinking, repeat the setting process from the
beginning.
9 When the setting is complete, press:
Model
Button
FTXP and ATXP
Keep
5 seconds.
Result: The user interface will return to the previous screen.
7

Commissioning

NOTICE
ALWAYS operate the unit with thermistors and/or pressure
sensors/switches. If NOT, burning of the compressor might
be the result.
(A)(F)TXP20~35M5V1B + FTXP20~35M5V1B9
Daikin room air conditioner
3P519299-4Q – 2020.06
,
and
a
b
pressed for about
7.1

Checklist before commissioning

After the installation of the unit, first check the items listed below.
Once all checks are fulfilled, the unit must be closed. Power-up the
unit after it is closed.
7.2

To perform a test run

Prerequisite: Power supply MUST be in the specified range.
Prerequisite: Test run may be performed in cooling or heating
mode.
Prerequisite: Test run should be performed in accordance with the
operation manual of the indoor unit to make sure that all functions
and parts are working properly.
1 In cooling mode, select the lowest programmable temperature.
In heating mode, select the highest programmable temperature.
Test run can be disabled if necessary.
2 When the test run is finished, set the temperature to a normal
level. In cooling mode: 26~28°C, in heating mode: 20~24°C.
3 The system stops operating 3  minutes after the unit is turned
OFF.
7.2.1

To perform a test run in winter season

When operating the air conditioner in Cooling mode in winter, set it
to test run operation using the following method.
For FTXP units
1 Press
,
, and
2 Press
.
3 Select
.
4 Press
.
5 Press
to switch the system on.
Result: Test run operation will stop automatically after about
30 minutes.
6 To stop operation, press
INFORMATION
Some of the functions CANNOT be used in the test run
operation mode.
If a power failure occurs during operation, the system automatically
restarts immediately after power is restored.