3. Installation and Wiring
3.8 External Protective Devices
For safety reasons, it is necessary to install an external circuit breaker at the input AC utility and to the battery.
3.8.1 External Battery
The UPS and its connected batteries are protected against the effects of over-current through a DC-compatible thermo-
magnetic circuit breaker located close to the battery.
3.8.2 UPS Output
Any external distribution board used for load distribution shall be fitted with protective devices to avoid the risk of UPS
overload.
3.8.3 Over-Current Protection
CAUTION!
• Wiring must be performed by qualified professional personnel.
• Before wiring or making any electrical connection, ensure the power supplied to the input and output of the UPS is cut off
completely and the internal battery connectors are disconnected.
• When connecting the UPS to the utility AC power and bypass source, protective devices and 3-pole connectors must be
installed. The protective devices and 3-pole contactors must use approved components that meet safety certifications. The
thermo-magnetic circuit breakers should be IEC 60947-2 trip curve C (normal). Refer below for required protective devices:
10kVA UPS: 50A circuit breaker required.
15kVA UPS: 63A circuit breaker required.
20kVA UPS: 80A input circuit breaker required.
• When connecting the critical loads to the UPS, a listed certified breaker must be installed between them. Refer to the below
for the required breakers:
10kVA UPS: 50A input breaker required.
15kVA UPS: 63A input breaker required.
20kVA UPS: 80A input breaker required.
• Check that the size, diameter, phase and polarity of each cable connecting to the UPS is correct. For the specifications of
input/output cables, refer to the table in section 3.9.2 UPS Internal Battery Cable Connectors.
3.9 Internal Battery Installation Procedure for UPS Models with No
Internal Batteries (-NIB Models)
DANGER! LETHAL HIGH-VOLTAGE HAZARD!
Even if not connected to the UPS system, there is potentially fatal high voltage inside the battery. Battery
connections should only be performed by qualified service personal, following all precautions listed in the
service manual, following local electrical codes.
17