Rs-232 Communication Port Definition; Rs-485 Communication Port - Tripp-Lite SmartOnline S3M10K1B Manual Del Propietário

Sistemas ups trifásicos
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

7. Communications

7.4 RS-232 Communication Port Definition

Notes:
• The USB, RS-232 and RS-485 interfaces cannot be used simultaneously. Only one interface can be used at a time.
• These three communication ports use a MODBUS protocol. Refer to the S3M10-20kVA 3-Phase MODBUS Owner's Manual. The
MODUBS manual may be downloaded from the specific S3M10-20K UPS model page at tripplite.com.
The RS-232 port is a male connector.
Connection Between the Connected Computer's RS-232 Port and UPS System's RS-232 Port
Computer RS-232 Port
Pin 2
Pin 3
Pin 5
Available Functions of the RS-232 Port
• Monitor UPS power status
• Monitor UPS alarm data
• Monitor UPS run parameters
• Timing off/on setting
• One-to-one communication, UPS to computer, at a distance less than 5 m
RS-232 communication data format
• Baud rate: 9600 bps
• Byte length: 8 bit
• End bit: 1 bit
• Parity check: None
7.5 RS-485 Communication Port Definition
Notes:
• The USB, RS-232 and RS-485 interfaces cannot be used simultaneously. Only one interface can be used at a time.
• These three communication ports use a MODBUS protocol. Refer to the S3M10-20kVA 3-Phase MODBUS Owner's Manual. The
MODUBS manual may be downloaded from the specific S3M10-20K UPS model page at tripplite.com.
The RS-458 Port is a female connector.
UPS RS-232 Port
Pin 2
Pin 3
Pin 5
66
UPS send, PC receive
PC send, UPS receive
Ground