4. Operation

4.3.6.2.1 System Setup

Click the System Setup icon. Select the configuration to be changed/saved. Click the Back icon to return to the previous
window, or click the Home Page icon to jump to the main page.
Advanced System Setup Configurations
Working Mode: Select the work mode of UPS, work mode: Single Mode, Parallel Mode, ECO Mode, ECO+Parallel Machine
Mode. Default value: ECO Mode.
Auto Turn-On: Select the UPS start logic. Enable: The UPS starts inverter output automatically. Disable: No output.
Note: If you want the UPS to auto restart after the batteries reach a low voltage cut-off and the UPS turns off, Auto Turn-on MUST be set to
Enable.
Figure 4-28A: Advanced System Setup
Freq Conv Mode: Frequency Conversion Mode. Enable: output frequency is 50 Hz or 60 Hz, input frequency is 60 Hz or
50 Hz, UPS no alarm no battery and bypass abnormal. Default: Disable.
LBS Mode: Setting values: LBS disable, LBS master, LBS slave. Default: LBS disable.
Float Temp. Compen: Temperature sensor compensation switch. To connect a battery temperature sensor, change the value
to enable.
Temp Sensor Select: Temperature sensor type selection. There are two choices: NTC and RS485. Use NTC for single and
short distances. Use RS485 for multiple and far distances.
Figure 4-28B: Advanced System Setup