8. Specifications

Model
OVERVIEW
Capacity
Topology
INPUT
Voltage and Phase
Voltage Range
Frequency (Range)
Power Factor
Harmonic Distortion
Dual AC Input
Backfeed Protection
OUTPUT
Voltage and Phase
AC Voltage Regulation
Power Factor
Frequency
Frequency Regulation
Overload (AC Mode)
Crest Factor
Harmonic Distortion
Waveform
Transfer Time
Parallel Capability
BYPASS
Bypass Voltage Range
Bypass Frequency Range
EFFICIENCY
Online Mode
ECO Mode
BATTERY AND CHARGER
DC Acceptance Voltage
Battery Configuration
Internal Battery Quantity
Run time (100% Load)
Run time (50% Load)
External Battery Pack (Cabinet)
Models
Charging Current (Default)
ENVIRONMENT
Operating Temperature
Storage Temperature
Operating Humidity
Operating Altitude
Audible Noise at 1 m
Heat Dissipation (100% Load)
MANAGEMENT
Display Panel
Communications
STANDARDS
Safety
EMC/EMI
Additional
PHYSICAL
Unit Dimensions (H x W x D)
Unit Weight
S3M25K
S3M30K
25 kVA/25 kW
30 kVA/30 kW
True On-Line Double Conversion; Voltage- and Frequency-Independent (VFI)
208/220V (Ph-Ph); 120/127V (Ph-N); 3-Phase, Neutral and Ground
-20%, +25% (Ph-Ph 166–260V or 176–275V) at 100% Load; -40%, +25% (Ph-Ph 125–260V or 132–275V) at <50% Load
208/220V (Ph-Ph); 120/127V (Ph-N); 3-Phase, Neutral and Ground
±1% of Nominal (Double-Conversion Mode, Converter Mode or Battery Mode); ±10% of Nominal (ECO Mode)
Selectable ±1%, ±2%, ±4%, ±5%, ±10% of Input (Default: ±5%)
Load ≤ 110%=1 hour; Load ≤ 125%=10 min.; Load ≤ 150%=1 min.; Load >150%=Bypass
≤ 2% THD (100% Linear Load); ≤ 5% THD (100% Non-Linear Load)
0 ms (Line ‹–› Battery and Inverter ‹–› Bypass); <8 ms (Battery ‹–› ECO)
Parallel up to 5N+1 Units for Increased Capacity or up to 6 for Redundancy
Upper Limit: +10%, +15%, +20% or +25% (Default: +20%); Lower Limit: -10%, -20%, -30% or -40% (Default: -40%)
External Only*
External Only*
None
None
UPS runtime depends on the connected loads and the battery pack/cabinet model. Refer to the model page at tripplite.com for runtimes.
1 – 20A (0.15C)
2 – 20A (0.15C)
< 1000 m (Derate output power by 1% per 100 m above 1000 m.)
< 65.4 dBA
< 67.8 dBA
6339 BTU/h
7679 BTU/h
Large 12.7 cm (5-inch) Multi-language Touchscreen Display with Supplemental LEDs
Optional SNMP Network Management Card (WEBCARDLX) and three integrated MODBUS Ports: RS-232, RS-485 (RJ45), USB.
UL1778:2014 (5th Edition); CAN/CSA-C22.2 No. 107.3-14 (3rd Edition)
ENERGY STAR 2.0, RETIE, IP20 Ingress Protection Rating; RoHS, ISTA 3B/Vibration, Shock and Tip tested.
39.4 x 11.8 x 31.5 inches/
1000 x 300 x 800 mm
209 lb. / 95 kg
212 lb. / 96 kg
S3M50K
S3M60K
50 kVA/50 kW
60 kVA/60 kW
50/60 Hz, Selectable (40 – 70 Hz)
≥ 0.99 (100% Linear Load); ≥ 0.98 (50% Linear Load)
< 3% THDi (100% Load)
Yes
Yes
1.0 (Unity Output Power Factor)
±0.1 Hz (Converter Mode or Battery Mode)
3:1 Maximum
Pure Sine Wave
±10% (Adjustable)
up to 94%
up to 98%
±120V DC (Nominal)
External Only*
External Only*
None
*Refer to section 3.9 UPS to Cabinet Model Compatibility
4 – 40A (0.15C)
4 – 40A (0.15C)
0 – 40˚ C
-15 – 60˚ C
0 – 95% (Non-Condensing)
< 72 dBA
< 72 dBA
12628 BTU/h
15154 BTU/h
The Relay I/O card is optional.
FCC Part 15B Class A
47.2 x 17.4 x 33.46 inches/
1200 x 442 x 850 mm
353 lb. / 160 kg
364 lb. / 165 kg
80
S3M80K
80 kVA/80 kW
External Only*
None
None
6 – 60A (0.15C)
< 74 dBA
19932 BTU/h
62.99 x 23.62 x 33.46 inches/
1600 x 600 x 850 mm
624 lb. / 283 kg
S3M100K
100 kVA/100 kW
External Only*
None
8 – 80A (0.15C)
< 75.6 dBA
24915 BTU/h
708 lb. / 321 kg