4. Operation
Inter Power Walk in(s): When the UPS systems are in parallel mode, this setting enables the UPS to control the interval that
each UPS transfers from battery mode to normal mode, reducing the impact on the generator or power grid. The value range is
1 to 200. The default value is 10.
Figure 4-28C: Advanced System Setup
4.3.6.2.2 Parallel Settings
Parallel ID: The Parallel ID must be modified after setting the work mode to parallel mode. The value range is 1 to 6. The
default value is 1.
Parallel for Capacity Units: Parallel cabinet number must be modified for the total number of parallel cabinets after setting
the work mode to parallel mode. The value range is 2 to 6. The default value is 2.
Parallel Redundancy Units: Parallel redundancy cabinet number can be modified after setting the work mode to parallel
mode. The value range is 0 to 5. The default value is 0.
Figure 4-29: Parallel Settings
57