Electrical Wiring; Wiring Procedure - Tuthill FILL-RITE FR700V Serie Manual De Instalación Y Operación

Bombas de transferencia de combustible
Ocultar thumbs Ver también para FILL-RITE FR700V Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

|
FR700V SERIES FUEL TRANSFER PUMPS

Electrical Wiring

WARNING! Electrical wiring should be performed ONLY by a licensed electrician in compliance with local, state, and national electrical code NEC/ANSI/NFPA
70, NFPA30, and NFPA 30A, as appropriate to the intended use of the pump. Threaded rigid conduit, sealed fittings, and conductor seal should be used. The
pump must be properly grounded. Improper installation or use of this pump can result in serious bodily injury, or death!
CAUTION! All pumps should be operated at the Rated Nameplate Voltage. Power should be supplied to the pump from a dedicated 20 amp circuit breaker. No
other equipment should be powered by this circuit. Wiring must be of sufficient size to carry the correct current for the pump. Voltage drop will vary with dis-
tance to pump and size of wire; refer to the National Electrical Code (NEC), or local codes, for Voltage Drop Compensation to be sure you are using the correct
size wire for your application.

Wiring Procedure

WARNING! The "AUX." wire IS A LIVE WIRE when the switch is on! The "AUX" lead wire is insulated and enclosed when shipped. DO NOT connect this wire with-
out first verifying the "ON" line voltage of the wire for compatibility with the equipment to be installed. Maximum amperage on this wire is 1 amp. The "AUX"
wire must be insulated and enclosed in the junction box if not used.
115 VOLT WIRE DIAGRAM AUX LEAD RATED 1.0 AMP
ORANGE
AUX
BLACK
AC
WHITE
NEU
GREEN
GRN
1. Remove the junction box cover and straighten the wires to make sure the stripped wire ends are accessible outside the junction box.
2. Connect the pump wires to the power supply lines according to the diagram. Be certain to properly insulate the connections with the appropriate wire nuts
or other connectors. Note that the ground wire MUST be connected.
3. Tuck the wires back into the junction box, verify proper placement of gasket, align cover with junction box holes and reinstall screws. Torque each screw to 90 ± 9 in-lbs.
IMPORTANT! Be certain the gasket for the cover is in place, and the screws draw the cover down tight over the junction box. There must be no gap between the junction box
and it's cover.
16
AWG
115V AC
39
(60 Hz motor)
230V AC
186
(50 Hz motor)
230V AC
170
(60 Hz motor)
230 VOLT WIRE DIAGRAM AUX LEAD RATED 1.0 AMP
ORANGE
AUX
BLACK
AC
BLACK WITH
WHITE STRIPE
AC
MOTOR
GREEN
GRN
Solid Wire
14
12
10
8
62
99
158
250
296
471
751
--
271
432
689
--
MOTOR
MAX CABLE LENGTH (FEET)
6
4
16
14
--
--
38
61
--
--
182
290
--
--
167
265
OFF
Conduit opening
1/2" NPT
ON
Stranded Wire
12
10
8
6
96
154
245
389
459
733
--
--
421
672
--
--
4
620
--
--

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido