Electric wiring and the application
Outdoor power source and power cable
Model
AWAU-YCV080-H11
AWAU-YCV150-H11
AWAU-YCV150-H13
AWAU-YCV180-H13
• Power cable must be fixed firmly.
• Each outdoor must be earthed well.
• When power cable exceeds the range, thichen it appropriately.
Indoor power source and communication wiring
Item
Power cable
Indoor
section
total
(mm
current (A)
<10
2
≥10 and <15
3.5
≥15 and <22
5.5
≥22 and <27
10
• Power cable and communication wire must be fixed firmly.
• Each indoor must be grounded well.
• When power cable exceeds the range, increase the gauge appropriately.
• Shielded layer of communication wires must be connected together and be earthed at single
point.
• The total length of communication wire cannot exceed 1000m.
Communication wire for wired controller
Length of Signal Line (m)
≤250
• The shielding lay of the signal line must be grounded at one end.
• The total length of the signal line shall not be more than 250m.
Item
Power
source
1PH,
220-230V~, 50Hz
1PH,
220-230V~,
50/60Hz
3N~,
380-400V, 50/60Hz
Rated current
Wire length
of overcurrent
(m)
2
)
23
24
27
42
Wiring Dimensions
2
0.75mm
× 3 core shielding line
Power cable
Circuit
section
breaker
2
(mm
)
(A)
6
25
16
50
4
20
4
20
Rated current of residual
circuit breaker(A)
breaker
Ground fault interruptor(mA)
(A)
response time(S)
20
20A, 30mA, below 0.1s
30
30A, 30mA, below 0.1s
40
40A, 30mA, below 0.1s
50
50A, 30mA, below 0.1s
15
Rated current of residual
circuit breaker (A)
Ground fault interruptor (mA)
response time (S)
25A 30mA below 0.1S
50A 30mA below 0.1S
20A 30mA below 0.1S
20A 30mA below 0.1S
Communication wire section
Outdoor/indoor
(mm
2-core × (0.75-2.0mm
Ground wire
Section
Screw
2
(mm
)
6
M5
16
M5
4
M5
4
M5
Indoor/indoor
2
2
)
(mm
)
2
)
shielded wire