CAUTION
The requirements of operating voltage and
frequency of all electronic equipment shall
be checked prior to plugging them into this
generator. Damage may occur if the equipment
is not designed to operate within a voltage variation
of +/-10% and frequency variation of +/-3 Hz of the
rating appearing on the nameplate of the generator.
In order to avoid damage, always have an additional
burden other than solid state load plugged into the
generator in case of using only solid state (such as
a television set) loads.
A line conditioner may be necessary for some
applications of solid state equipment.
INSTALLATION
WARNING
To avoid possible personal injury or property
damage, it is necessary that the installation and
all service be performed by a qualified electrician
or authorized service representative. Under no
circumstances shall be permitted that a non
qualified person make cable or wiring works into the
electrical utility circuits.
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
All manuals and user guides at all-guides.com
In order to avoid the feedback to the electrical utility
1
systems, isolation of the location or facility electrical
system is required.
2
Before make the temporary connection of the generator
to the location or facility electrical system, turn off or
disconnect the main service.
3
If the generator is to be used as a source of backup power
in the event of a power failure, it must be installed by a
licensed electrician in accordance with all applicable local
electrical codes.
4
Proper use requires the installation of a transfer switch
double throw by a qualified electrician trained and qualified
to ensure that the building's electrical circuits may be
switched safely between utility power and the generator's
output, avoiding the feedback to the power supply system.
WARNING
To avoid feedback towards the power supply
systems, isolation of the location or facility
electrical system is required. Before temporary
connection of the generator to the location or
facility electrical system, turn off the main switch.
Before making permanent connections, you must install
a double-throw transfer switch. To avoid electrocution or
property damage, only qualified electricians can connect
the generator to the location or facility electrical system.
California laws require the isolation of the residence
electrical system before connecting a generator to the
residential electrical systems.
Always follow the codes and ordinances that apply
5
to the installation of any equipment related to this
product.
NFPA 70 - National Electrical Code.
NFPA 30 - Standard for installation and use of
stationary engines of fuel.
Agricultural facilities wiring manual for auxiliary electric
power for farms.
ELECTRICAL EXTENSIONS
All loads supplied from the generator will be connected
1
to the panel using extensions or cables and it must be
done by means of 3-prong grounded 125 volts 15A
and 20 A plugs,
30 A twist lock plugs, or 4-prong grounded 125/250 V
50 A. The receptacles must not be loaded above the
amperage rating.
4-prong grounded 125/250 volts
5-15P
L14-30P
5-20P
14-50P
9