Installer Setting - Thermistor - LG PREMTB10U Manual Del Usuario

Ocultar thumbs Ver también para PREMTB10U:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Installer Setting - Thermistor

This is a function to determine if you will use the indoor unit mounted sensor or the thermostat
sensor.
<Thermistor Table>
Temperature sensor selection
01
Thermostat
02
Indoor unit
Cooling
03
2TH
Heating
h The function of 2TH has different operation characteristics according to the product.
h For the indoor temperature below 10 °F, it displays the value perceived by the sensor of the
Thermostat regardless of the temperature sensor setting.
Press the
1
enter Thermostat installer setup mode.
- If pressed for a shorter time, it enters
into user setup mode.
If moving to room temperature perception
2
sensor selection menu by pressing
button, it indicates as picture below.
Set Thermistor value by pressing
3
buttons. (01: Thermostat,
02: Indoor, 03: 2TH)
Function Code
Press
4
Press
5
After setup, it automatically exits after 25
seconds if there is no input. If the
Setting/Cancel button is not pressed, the
mode will not change.
Operate according to Thermostat temperature sensor
Operate according to indoor unit temperature sensor
Operate according to higher temperature by comparing indoor
unit's and Thermostat's temperature.
(There are products that operate at a lower temperature.)
Operate according to lower temperature by comparing indoor
unit's and Thermostat's temperature.
INSTALLATION INSTRUCTIONS
button for 3 seconds to
Thermistor setting
button to save.
button to exit settings mode.