The proper device to use depends on mains configuration; for
X8 Powersoft suggests:
single-phase AC (P+N+E): 32 A rating, C or D curve, 10 kA;
three-phase AC (3P+N+E): 4 x 16 A rating, C or D curve, 10 kA.
For X4 Powersoft suggests:
single-phase AC (P+N+E): 16 A rating, C or D curve, 10 kA;
three-phase AC (3P+N+E): 4 x 10 A rating, C or D curve, 10 kA.
NOTE: The pictures and instructions about AC wiring refer to the
European CENELEC standards April 2004 (IEC 60446) color code for
conductor identification (see
TAB.
Conductor
Neutral or mid-point conductor
AC phase conductors
Protective conductor (earth)
TAB. 1: Color code for conductor identification.
AC mains connections must be performed
only by professional or qualified personnel
according to local electrical authoritie guidelines.
3 : 4.1. Three-phase electric power
Each
single
conductor
PC 5/5-STF1-7,62 flying plug as shown in
instances neutral connection may lack: on three-phase systems
neutral connection is not even necessary given the capability of the
X Series to work in delta connection.
3 : 4.2. Two-phase electric power
Balanced
two-phase
AC
tions 2P+E without neutral must be secured to the
PC 5/5-STF1-7,62 flying plug as shown in
care to double the phase wires at the connecting terminals of the
sectioning breaker in order to guarantee the proper conduction
gauge.
3 : 4.3. Single-phase electric power
P+N+E, unbalanced single-phase with neutral is the usual
configuration for signle-phase AC mains; wiring must be config-
ured as shown in
Panel L, p.
13. Take care to double the phase
and neutral wires at the connecting terminals of the sectioning
breaker in order to guarantee the proper conduction gauge.
1).
Color
N
blue
L1
brown
L2
black
L3
grey
green/
E
yellow
must
be
secured
to
the
Panel K, p.
13. In some
mains
in
the
configura-
Panel M, p.
14. Take
3 : 5.Precautions regarding installation
WARNING: TO PREVENT FIRE OR ELECTRIC SHOCK
f This device must be powered exclusively by earth connect-
X
ed mains sockets in electrical networks compliant to the IEC
364 or similar rules.
f Install the unit into rack cabinet only.
X
f A sectioning breaker between the mains connections and
X
the amplifier must be installed inside the rack cabinet.
f Take care to properly lock each power cord wire to the flying
X
connector Phoenix PC 5/5-STF1-7,62.
f Once properly wired, insert and lock the flying connector
X
into the shell provided by Powersoft.
f Lock the flying connector to the amplifier inlet.
X
f Before powering this amplifier, verify that the correct volt-
X
age rating is being used.
f Verify that your mains connection is capable of satisfying
X
the power ratings of the device.
f Do not use this amplifier if the electrical power cord is
X
frayed or broken.
f Output terminals are hazardous: wiring connection to these
X
terminals require installation by an instructed person and
the use of ready-made leads.
f Take care to lock the output terminal before switching the
X
device on.
f To avoid electrical shock, do not touch any exposed speaker
X
wiring while the amplifier is operating.
f Do not spill water or other liquids into or on the amplifier.
X
f No naked flame sources such as lighted candles should be
X
placed on the amplifier.
f Do not remove the cover. Failing to do so will expose you to
X
potentially dangerous voltage.
f The manufacturer cannot be held responsible for damages
X
caused to persons, things or data due to an improper or
missing ground connection.
f Contact the authorized service center for ordinary and ex-
X
traordinary maintenance.
It is absolutely necessary to verify these fundamental
requirement of safety and, in case of doubt, require
an accurate check by qualified personnel.