Technical Data; Burner Equipment - Riello 40 G20S Instrucciones De Instalación, Montaje Y Funcionamiento

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

TECHNICAL DATA

TYPE
Thermal power – output
Fuel
Electrical supply
Motor
Capacitor
Ignition transformer
Pump
Absorbed electrical power
Burner with CE marking in conformity with EEC Directives: Machine Directive 2006/42/EC, Low Voltage
Directive 2006/95/EC, Electromagnetic Compatibility 2004/108/EC and Efficiency 92/42/EEC.
The burner meets protection level of IP 40, EN 60529.
1 – Return line
2 – Suction line
3 – Gauge connection
4 – Pump pressure regulator
5 – Vacuum gauge connection
6 – Hydraulic jack with air-damper
7 – Combustion head adjustment screw
8 – Reset button with lock-out lamp
9 – Flange with insulating gasket
10 – Start delaying device
2406
482 T58
95 – 240 kW
-
Light oil, viscosity 4 – 6 mm
Single phase,
220 V
Run current 2.2 A – 3250 rpm – 340 rad/s
4 µF
Secondary 8 kV – 16 mA
Pressure 8 – 15 bar
0.41 kW
Fig. 1
D8077

BURNER EQUIPMENT

Quantity
2
1
4
1
1
1
1
GB
8 – 20 kg/h
2
/s at 20 °C
~
±
10%
60Hz
Description
Flexible pipes with nipples
Flange with insulating gasket
Screws and nuts for flange
Maintenance assembly
Cable grommet
Screw with two nuts for flange
ENGLISH

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

3748259