4.4

Technical data

Model
Thermal output
(1)
Fuel
Operation
Use
Ambient temperature
Combustion air temperature
Noise levels
Sound pressure
(2)
Sound power
Weight
Reference conditions: Temperature 20°C - Barometric pressure 1013 mbar – Altitude 0 m above sea level.
(1)
Sound pressure measured in manufacturer's combustion laboratory, with burner operating on test boiler and at maximum output.
(2)
The sound power is measured with the "Free Field" method, as per EN 15036, and according to an accurate "Accuracy: Category 3" measurement,
as described in EN ISO 3746.
4.5

Electrical data

Model
Electrical power supply
Fan motor
Ignition transformer
Capacitor
Absorbed electric power
Protection level
20141167
Technical description of the burner
kW
Mcal/h
Gas
G20
°C
°C max
dB(A)
kg
1~ 220-230V 50 Hz
rpm
rad/s
A
F
kW
8
GB
RS5F
160 ÷ 330
13.76 ÷ 28.38
3
NCV 8  12 kWh/m
– 7.000 10.340 kcal/m
Pressure: min. 20 mbar – max. 100 mbar
Intermittent (FS1)
Boilers: water and diathermic oil
0 - 40
40
71
82
18 - 20
RS5F
2720
288
1.9
Primary 230V – 0.2A
Secondary 18 kV / 11 mA
8.0
0.43
IP40
3
Tab. C
1~ 220-230V 60 Hz
3320
347
2.3
0.60
Tab. D