Switching Frequency
configuration (configuration 110: 2 kHz, configuration 410: 4 kHz). Higher switching frequencies
reduce the noise of the motor but require a reduction of the output current (see technical data in
the operating instructions manual).
Setting:
Min. Switching Frequency
automatically in the case of a thermal overload of the frequency inverter.
Setting:
Minimum Frequency
S2IND, S3IND results in an acceleration of the drive to the minimum frequency.
Setting:
Maximum Frequency
quency of the frequency inverter.
Setting:
Acceleration (Clockwise)
output frequency is changed after a start, stop or brake command or when the reference value is
changed.
Setting:
Operation Mode
cording to the connected signal source.
Setting:
Fixed Frequency 1
cies is effected via the fixed frequency change over function of the multi-function input MFI1.
Operation Mode
S5IND, the fixed frequency in one of the four data sets can be selected.
Up to 8 fixed frequencies can be parameterized and selected via the control of the digital inputs.
Setting:
Op. Mode Digital Output 1
functions can be assigned to the digital output S1OUT and the relay output S3OUT.
Setting:
Analog Operation
which is proportional to an actual value.
Setting:
09/08
09/08
400 - The factory setting of the switching frequency is dependent on the
2 kHz, 4 kHz, 8 kHz, 12 kHz, 16 kHz
401 – defines the minimum value the switching frequency is reduced
2 kHz, 4 kHz, 8 kHz, 12 kHz, 16 kHz
418 - the start command entered via the control unit or digital inputs
0.00 Hz ... 999.99 Hz
419 - The speed range of the drive is limited by the maximum output fre-
0.00 Hz ... 999.99 Hz
Deceleration (Clockwise)
420,
0.00 Hz/s ... 9999.99 Hz/s
452 (for multi-function input); the set point at input MFI1 can be adjusted ac-
1 -
voltage signal, 0 V ... 10 V (factory setting)
2 -
current signal, 0 mA ... 20 mA
3 -
digital fixed frequency change-over, 0 V ... 24 V, digital input
Fixed Frequency 2
480,
452 (multi-function input on setting 3). Via the data set change-over S4IND,
-999.99 Hz ... 999.99 Hz
Op. Mode Digital Output 3
530,
0 -
switched off
2 -
run signal, drive turning/not turning message
3 -
fault message
11 -
Warning
41 -
trigger electro-mechanical brake
1xx -
inverted operation mode (LOW active)
553 - output MFO1 supplies a pulse width modulated signal (0 V ... 10 V)
7 -
actual frequency, 0 Hz ...
20 -
active current, 0 A ... I
30 -
active power P
, 0 kW ...
wirk
50 -
effective current, 0 A ... I
52 -
machine voltage, 0 V ... 1000 V
421 - the ramps define how fast the
481 - change-over between the two fixed frequen-
532 - various control and monitoring
Maximum Frequency
419
FIN
Rated Mech. Power
376
FIN
41
41