Temperature coefficient:
Intrinsic error:
Operating error:
Climatic class:
Housing:
EMC
Emission:
Immunity:
Power supply:
Operation time with
battery:
Dimensions:
Weight:
Safety
Safety:
Pollution Degree:
Protection:
RMS values are measured with a 20 ms resolution.
V-RMS Wye Measurement
Measuring range:
Intrinsic error:
Operating error:
Resolution:
V-RMS Delta Measurement
Measuring range:
Intrinsic error:
Operating error:
Resolution:
A-RMS Measurement
Flexi Sets and current probes with voltage output are supported. All current probes must
correspond to 600 V / CAT III
±0.1 % of the measured value per K.
Refers to reference temperature, max. deviation is
guaranteed for 2 years.
Refers to operating temperature range, max. deviation is
guaranteed for 2 years.
C1 (IEC 654-1) -5 °C to +45 °C, 5 % to 95 % RH, no dew
Cycoloy shock and scratch proof thermoplast V0-type (non-
flammable) with rubber protection holster
IEC 61326-1:2006 class B
IEC 61326-1:2006
NiMH battery-pack, with ac adapter (15 V to 20 V/0.8 A)
Typical >8 h with bright backlight, >10 h with low backlight,
and 24 h without backlight
240 x 180 x 110 mm (6.1 x 4.6 x 2.8 in)
1.7 kg (3.75 lb), including battery
EN/IEC 61010-1:2001 (2
enforced insulation
2
IP65; EN60529 (refers only to the main housing without the
battery compartment)
57 / 66 / 110 / 120 / 127 / 220 / 230/ 240 / 260 / 277 / 347 /
380 / 400 / 417 / 480 V AC
±(0.2 % of measured value. + 5 digits)
±(0.5 % of m. v. + 10 digit)
0.1 V
100 / 115 / 190 /208 / 220 / 380 / 400 / 415 / 450 / 480 / 600 /
660 / 690 / 720 / 830 V AC
±(0.2 % of m. v. + 5 digit)
±(0.5 % of m. v. + 10 digit)
0.1 V
nd
ed.) 600 V CAT III, double or
Power Logger
Specifications