FLUE EXHAUST INSTALLATION
CONCENTRIC FLUE PIPE
Fit the concentric elbow pipe positioning it in the desired direction and insert the sealing gasket on it.
Fit the air intake and flue pipes, observing the distances indicated on the installation diagram. The flue
pipe should slope slightly upward ( a gradient of about 3%) and outward so that any condensation
which forms in the boiler can be collected.
DOUBLE FLUE PIPE
The flue pipe should slope slightly upward ( a gradient of about 3%) and outward so that any condensation
which forms in the boiler can be collected.
ATTENTION: Use only air intake/ fumes evacuation kits produced by Lamborghini Caloreclima.
All manuals and user guides at all-guides.com
Installing an elbow to connect the boiler to the chimney will cau-
se a drop in pressure.
The values set out in the table below indicate the necessary
reduction to the length of the linear pipes.
TYPE OF
INSTALLATION
CONCENTRIC FLUE
EXHAUST
DOUBLE FLUE PIPE
(INTAKE/EXHAUST)
G CONCENTRIC FLUE
EXHAUST: max length 3 m
G DOUBLE FLUE PIPE (Intake +
Delivery): max length 50 m.
90° ELBOW
45° ELBOW
FITTED
1 m.
0.6 m.
41
FITTED
0.5 m.
0.3 m.