WATER SUPPLY CONNECTION
Fit the assembly template up against the wall. Then fit all the piping: system delivery, system return,
cold water, hot water, gas, condensation discharge and electrical power supply for the room thermostat.
Once the pipes have been fitted the end fittings can be unscrewed and ordinary plugs can be inserted
ready for water supply tests to be carried out.
CONDENSATION DISCHARGE
The condensation which forms inside the boiler must be discharged. The boiler is fitted with a condensation
trap. The trap fitting must be connected to a Ø 32 mm PVC outlet pipe. It is advisable to instal a second
trap upstream from the plumbing system.
Important: When replacing the
condensation discharge pipe,
supplied with the boiler, use a
pipe with an internal diameter of
13 mm.
Maximum external dimensions
of discharge: Ø 70 mm max.
and H 25 mm max.
LEGEND
C
Hot water Ø 1/2"
G Gas Ø 3/4"
F
Boiler water supply Ø 1/2" (cold)
AE Electrical supply
M System delivery Ø 3/4"
R
System return Ø 3/4"
SC Condensation discharge Ø 80 mm
NOTE: Preview hydraulic female connections.
All manuals and user guides at all-guides.com
Comfort water supply connection kit (available on
request)
36