Parameter
CnF
CP
FAn
ALL
Note: while the parameters are being set, the COMPRESSOR and ELECTRIC RESISTOR LEDs flash, alternating with
the DEFROSTING LED.

ALARM DISPLAY

MALFUNCTION
Values display indication
E00
Values display indication
E01
Values display indication
E02
Values display indication
E04
Values display indication
E07
30
English 07/03
LIST OF ACCESSIBLE - DISPLAYABLE PARAMETERS
Description
Appliance configuration parameters
Compressor parameters
Fan parameters
Alarm parameters
Remote switch set to OFF
(automatic reset)
High pressure switch tripped.
manual reset after three trips in an hour
High pressure switch tripped.
automatic reset for the first three trips in an hour
Compressor and/or fan thermal overload switch
tripped (manual reset)
BP3 pressure transducer fault
(automatic reset)
CAUSE
Unit of measurement
Value
Value
Value
Value
REMEDY
Position the remote switch to ON
Reset the switch
Reset the jumper between terminals 6 and 7
Check for fault (see high discharge pressure
page 31)
Reset manually
Check for fault
Verify compressor motor and/or fan motor
Reset manually
Check electrical connections
Replace component