Motor controller
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
This product is listed by Underwriters Laboratories Inc.
(UL). Representative samples of this product have been
evaluated by UL and meet applicable UL requirements.
UL approval information
CMMP-AS-...
Product category code
NMMS (USA),
NMMS7 (Canada)
File number
E198574
Considered standards
UL 508C
UL 61800-5-1
C22.2 No. 274-2013
UL mark
Product category
Ind. Cont. Eq.
(Industrial Control Equipment),
Control number
1UD1
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Fitting and commissioning is to be carried out by quali-
fied personnel only in accordance with the operating
instructions.
Such qualified personnel must have several years of
training and experience in installing and commissioning
electrical and pneumatic industrial control systems.
• Please observe the applicable safety requirements
and standards.
Extracts )* from the UL report:
Electrical Ratings
CMMP-AS-
C2-3A-...
C5-3A-...
C5-11A
C10-11A
-P3-...
-P3-...
Input voltage
100-230
100-230
230-480
230-480
(rms/_10 %)
V
V
V
V
AC
AC
AC
Input current
3...2 A
6...4 A
5.5 A
10 A
Frequency
50-60 Hz
(Input)
Phase
1~
1~
3~
3~
Output
0-270 V
0-270 V
0-360 V
0-360 V
AC
AC
AC
voltage
(rms/max)
Output
2.5 A
5 A
5 A
10 A
current
Frequency
0-1000 Hz
(Output)
Max. surroun-
40°C/104°F
ding air tem-
perature
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Circuit protection
Branch Circuit Protection has to be provided in the field.
The following fuse sizes shall be used.
– Listed Circuit Breaker according UL 489, rated 277 Vac,
16 A, SCR 10 kA.
Wiring and environment regards for
CMMP-AS-C2-3A-.../CMMP-AS-C5-3A-...:
– Use 60/75 or 75 °C copper (CU) wire only.
– The terminal tightening torque is 0.22...0.25 Nm.
– To be used in a Pollution Degree 2 environment only.
Wiring and environment regards for
CMMP-AS-C5-11A-P3-.../CMMP-AS-C10-11A-P3-...:
– Use 60/75 or 75 °C copper (CU) wire only.
– The terminal tightening torque is 0.5...0.6 Nm.
– To be used in a Pollution Degree 2 environment only.
– For use with grounded wye sources only.
Motor temperature sensor
Note
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Motor overtemperature sensing is not provided by the
drive.
For protection against excess temperatures, the UL-certi-
fied servo positioning controllers (recognisable by the UL
or cUL test symbol on the name plate) may only be used in
combination with motors that have an integrated motor
temperature sensor. Temperature monitoring must be
activated correspondingly through the software.
AC
AC
)* taken over essentially without important changes
en
Note