Chapter 5
Table 2. Avaya 240 Vdc Extended Battery Cabinet Technical Specifications
Battery Type
Expected Life
Nominal Battery String Voltage
Nominal Float Voltage
Recharge Current
Charger AC Input
Circuit Protection
Alarm Contact
Dimensions
(WxDxH)
Weight
Operating Environment
Agency Approvals
Avaya EBC240 Site Preparation, Installation and Operator's Manual
Specifications
Temperature: 0°C to 35°C (32°F to 95°F)
Recommended use: 25°C (77°F)
Humidity: 5 to 95% (noncondensing)
Safety: EN 50091-1-1, IEC 60950
EMC:
Valve-regulated lead acid (VRLA)
8–10 years
240 Vdc
2.3V/cell
2.2A per 240 Vdc per string
6A, 100–120 Vac, 50/60 Hz or
3A, 200–240 Vac, 50/60 Hz
Circuit breaker protection
300V, 25A
×
×
64.8
71.6
71.4 cm
×
×
25.5"
28.2"
28.1"
440 kg (970 lb)
For each 8°C (15°F) rise in temperature, the battery loses
approximately 50% of its rated life.
UL 1778
CSA-C22.2 No. 107.1-M91
FCC Part 15 Class A
CISPR 22 Class A, ICES-003
EN 50082-1, IEC 801-2, -3, -4
EN 50091-2
S
27
164201531 Rev C