Electric Control Cabinet; Wiring For Output Control Lines; Specification Of Power Cord And Air Switch - Gree D Serie Manual Del Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

6 Electric Control Cabinet

6.1 Wiring for Output Control Lines

Note:
The output control lines of the auxiliary electric heater 1, auxiliary electric heater 2 and the
water pump AC contactor are allowed to the terminal boards 11/12/13/14/15/16 of any module.

6.2 Specification of Power Cord and Air Switch

Model
LSQWRF65M/D-M
LSQWRF65M/NaD-M
LSQWRF80M/D-M
LSQWRF80M/NaD-M
LSQWRF130M/D-M
LSQWRF130M/NaD-M
LSQWRF160M/D-M
LSQWRF160M/NaD-M
Notes:
The specifications of the minimal size of the neural line should be 4mm
selected size of the neutral line should be equal to or larger than 4mm
The specifications of the breaker and power cable listed in the table above are determined
based on the maximum power (maximum amps) of the unit.
The specifications of the power cable listed in the table above are applied to the conduit-
guarded multi-wire copper cable (like, JYV copper cable, consisting of PV insulated wires
and a PVC cable jacket) used at 40℃ and resistible to 90℃ (see IEC60364-5-523:1999).
If the working condition changes, they should be modified according to the related
national standard.
The specifications of the breaker listed in the table above are applied to the breaker with
the working temperature at 40℃ . If the working condition changes, they should be modified
according to the related national standard.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
D Series Modular Air-cooled Scroll Chillers Owner's Manual
Power Supply
Live Line
380-415V 3N 50Hz
Min. sectional area of
the power cable (mm
Neutral Line
16
4
25
4
50
4
70
4
26
Capability of
2
)
the Air Switch
(A)
Earth Line
16
63
16
80
25
125
35
160
2
, that is, the
2
.