D Series Modular Air-cooled Scroll Chillers Owner's Manual
a. The voltage is too high or too low
b. The discharge pressrue is too high or too
low
Overload
c. The backwater temperature is too high
protection
d. The overloaded elment malfunctions
e. The ambient temperateure is too high
f. The motor and wiring terminal is short-
circuited
a. The voltage is too high or too low
b. The discharge pressure is too high
Internal over-
c. The entering chilled water temperature is
temperature
too high
protection
d. The internal overtemperature protection
device malfunctions
e. Refrigerant is charged insufficiently
a. The check valve or the drier-filter is clogged
Low pressure
b. The expanson valve malfunctions
protection
c. The low pressure switch malfunctions
d. Refrigerant is charged insufficiently
a. The circuit breaker trips or the fuse is
blown out
b. The control circuit fails to get through
c. There is no electric currrent
d. High or low pressure protection acts
e. The contact coil is blown out.
Failure to
f. Power phase is wired improperly
startup
g. The water system malfunctions and the
flow switch is opened
h. An alarm is raised on the wired controller
i. The ON/OFF Timer is improperly set
j. The temperature sensor is set out of the
set point
WARNING!
Without commissioning, warranty will turned invalid under the following conditions:
(1) Refrigerant leaks in that the user personally opens some valve or pipe connector.
(2) The user personally dismantles the unit without Gree's approval.
(3) The user personally powers the control cabinet or the compressor motor.
(4) The user personally charges oil or refrigerant to the unit.
(5) The user personally starts up the system.
(6) The user personally passes directly hot water or steam to the evaporator.
(7) The user fails to operate the unit following the instructions covered in this manual.

8.2 After-sales Service

When the unit in warranty has a quality issue or fails to operate properly under the allowable
operation condition, please contact the local sales representative for free service.
The user is required to designate personnel to take charge of the unit following the instructions
covered in this manual, otherwise any maintenance cost caused by the improper operation will be
at the user's expense.
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
a. Check the voltage which is required to be within
the rated value ±20V and the exceedance of
the phase difference to be within ±30%
b. Check the discharge pressure and figure out why
c. Check the backwater temperature and
figure out why
d. Check the electric current of the compressor
e. Improve the ventilation
f. Check the corresponding resistance of the
motor and the terminal
a. Check the voltage which is required to be
within the allowable range
b. Check the discharge pressure and figure
out why
c. Check the entering chilled water and figure
out why
d. Take the leakage test
a. Replace the check valve or the drier-filter
b. Adjust or replace the expansion valve
c. Check the low presure switch
d. Add refrigerant
a. Replace the damaged element
b. Check the wiring of the control system
c. Check the power supply
d. See "Too high discharge pressure", "Too low
discharge pressure", "Too high discharge
pressure", and "Too low discharge pressure"
e. Replace the damaged element
f. Rewire the power phase
g. Check the water system
h. Check the alarm type and take countermeasures