(2) Keep drainage pipe short and sloping downwards at a gradient of at least 1% for preventing
forming air bubbles.
(3) Insert the drainage hose into drain socket and then tighten the metal clamp securely.
(4) Warp the sealing pad over drainage hose and metal clamp for heat insulation.
(5) Make sure to perform insulation work for all drainage hoses in the room in order to prevent
any possible water dropping due to dew condensation.
(6) Apply the suitable diameter for converging drainage pipe according to the operating capacity
of the unit, as show in Fig 4.3.2.1.
① - Drainage pipes assembled by T-shaped joints
Copyright 2018. This translation is property of GREE PRODUCTS SL. All rights reserved. Total or partial reproduction without its express authorization is prohibited.
Multi Variable Air Conditioners Floor and Ceiling Type Indoor Unit