5.3
ELECTRICAL CONNECTIONS
Carry out the electrical wiring after having turned the power off in compliance
with the current safety regulations following the diagram of the figure 6 and
its caption.
Check that the power supply corresponds to the rated power reported
on the unit nameplate.
Electric connections in dotted lines should be carried out by the installer.
Each fan-coil requires a switch (IL) on the feeder line with a distance of at
least 3 mm between the opening contacts, and a suitable safety fuse (F).
On the wiring diagram the following abbreviations are used:
BK
Black = max. speed
BU
Blue = medium speed
CN
Fast-on connector
F
Fuse, not supplied
GNYE Yellow/Green = earth
IL
Line switch, not supplied
M
Motor
RD
Red = min. speed
WH White = common
1
To command (accessory)
6
TEST RUN
Check that the unit is perfectly levelled and that the drain pipe is not
obstructed (rubble deposits, etc.).
Check that the water connections (to the heat exchanger and water
drainage) are sealed.
Check that the electrical wiring is perfectly tight.
Be sure that the air purge of the heat exchanger has been carried out.
Replace the cabinet (where existing).
Turn on the power supply and check the unit running.
7
USE
To use the fan coil unit, refer to the instructions of the control panel,
available as accessory.
Air outlet grids on the cover cabinet (FL and FU) can be turned 180° to direct
the flow into the room or towards the wall on which the unit is mounted.
The grids and the side doors are snapped onto the cabinet. Before
removing them in order to change their position, cut the power off and wear
protective gloves.
8
MAINTENANCE
For safety reasons before carrying out any maintenance or
cleaning operation, switch off the unit turning the selection
switch to "Stop" and the power supply switch on position 0 (OFF).
Be careful during any maintenance operation; you could get
injured by some metal parts; use protective work gloves.
The estro fan coils do no require any particular maintenance operation:
only the periodical cleaning of the air filter should be carried out.
It is necessary to carry out a running in period of 100 hours in order to
eliminate all mechanical friction.
The starting up must be carried out at the maximum speed.
For good operation of the estro fan coils follow the instructions below:
- keep the air filter clean;
- do not pour liquids into the unit;
- do not introduce metal parts through the air outlet grid.
- keep the air inlet and outlet free at all times.
Each time the machine is turned on after being idle for a long period, ensure
there is no air in the heat exchanger.
Before using the unit for air conditions, check that:
- condensate drainage is performed correctly:
- the heat exchanger fins are not obstructed by deposits of dirt.
If necessary clean the fins with low pressure compressed air or steam
without damaging them.
È severamente vietata la riproduzione anche parziale di questo manuale / All copying, even partial, of this manual is strictly forbidden
9
CLEANING
For safety reasons before carrying out any maintenance or cleaning
operation switch off the unit turning the selection switch to "Stop" and
the power supply switch on 0 (OFF).
Clean the filter at least once a month and in any case before using the unit
(before the heating or the air conditioning season).
For cleaning the air filter proceed as follows (figure 7, page 20):
- model FL: turn the screws 90°, which secure the filter to the cover
cabinet, to 1/4 turn and remove the filter;
- flush-mounted model FC: reach the fan coil through the inspection panel
and remove the filter, turning the locking brackets 90°;
- model FU: remove the air filters that are inside the intake grids located
on the front panel of the cover cabinet;
- clean the filter with lukewarm water , or in case of dry dust, with
compressed air;
- reassemble the filter after having dried it up.
It is recommended to replace the air filter yearly, and to use original spare
parts.; the fan coil model is reported on the nameplate located on the
internal part of the side panel of the unit.
To clean the unit cabinet proceed as follows:
- use a soft cloth;
- do not pour any liquid on the unit, as this could cause electrical shocks
or damage the components inside it;
- do not use any aggressive chemical solvents; do not use very hot water
to clean the air outlet grid.
10

TROUBLESHOOTING

If the unit does not work properly first check the points reported in the
table below before requesting service. If the problem cannot be solved
contact your dealer or service centre.
Problems
Cause
The unit does not run at all
1 Power failure
2 Leakage breaker tripped
3 The switch is on STOP
position
Poor cooling or heating
1 Dirty or clogged air filter
performance
2 Obstacle near the air inlet or
outlet
3 Air inside the heat exchanger
4 Doors and windows are open
5 The unit is running at low
speed
The unit leaks
1 The unit is not levelled
2 Drip tray is clogged
5
GB
Solution
1 Restore power
2 Contact service centre
3 Turn on the unit selecting "I"
1 Clean air filter
2 Remove the obstacle
3 Contact the installer
4 Close doors and windows
5 Select medium or high fan
speed
1 Contact the installer
2 Contact the installer
FC66000611 - 04